In addition to what is explained below, the safety and installation information provided in the 

installation manual must be read and followed. The technical documentation and the interface 

and management software for the product are available at the website.

The device must be used in the manner described in the manual. If this is not the case the 

safety devices guaranteed by the inverter might be ineffective.

Quick Installation Guide

PVI-3.0/3.6/4.2-TL-OUTD

ABB Solar inverters

1.

Labels and Symbols

Inverter Models and Components

2.

Lifting and transport

4.

Choice of installation location

EN 

Assembly Instruction

6.

List of supplied components

3.

Choice of installation location

5.

Input configuration (DC)

7.

The labels on the inverter have the Agency marking, main technical data and identification of the equipment and manufacturer

 

V

dc max

I

dc max

V

dc MPP

V

dc, Full Power

I

sc max

V

acr

f

r

I

ac max

P

acr (cos 

φ 

= ±0.9)

P

acr (cos 

φ 

= 1)

MODEL:

PVI-3.0-TL-OUTD

IP65

5 minutes

600 V

90 - 580 V

2 x 10 A

160 - 530 V

2 x 12.5 A

Made in Italy

DIN V VDE 0126-1-1

PROTECTIVE CLASS: I

230 V 1Ø

50 Hz

3000W @ 45°C amb.

3000 W @ 50°C amb.

14.5 A

-25 to +60 °C

-13 to +140 °F

SOLAR INVERTER

www.abb.com/solar

                 

V

dc max

I

dc max

V

dc MPP

V

dc, Full Power

I

sc max

V

acr

f

r

I

ac max

P

acr (cos 

φ 

= ±0.9)

P

acr (cos 

φ 

= 1)

MODEL:

PVI-3.6-TL-OUTD

IP65

5 minutes

600 V

90 - 580 V

2 x 16 A

120 - 530 V

2 x 20 A

Made in Italy

DIN V VDE 0126-1-1

PROTECTIVE CLASS: I

230 V 1Ø

50 Hz

3600W @ 50°C amb.

3600 W @ 55°C amb.

17.2 A(*)

(*): 16 A for UK G83 Version

-25 to +60 °C

-13 to +140 °F

SOLAR INVERTER

www.abb.com/solar

                

V

dc max

I

dc max

V

dc MPP

V

dc, Full Power

I

sc max

V

acr

f

r

I

ac max

P

acr (cos 

φ 

= ±0.9)

P

acr (cos 

φ 

= 1)

MODEL:

PVI-4.2-TL-OUTD

IP65

5 minutes

600 V

90 - 580 V

2 x 16 A

140 - 530 V

2 x 20 A

Made in Italy

DIN V VDE 0126-1-1

PROTECTIVE CLASS: I

230 V 1Ø

50 Hz

4200W @ 45°C amb.

4200 W @ 50°C amb.

20 A

-25 to +60 °C

-13 to +140 °F

SOLAR INVERTER

www.abb.com/solar

The labels attached to the equipment must NOT be removed, damaged, dirtied, hidden,etc...

If the service password is requested, the field to be used is the serial number -SN: YYWWSSSSSS-

In the manual and/or in some cases on the equipment, the danger or hazard zones are indicated with signs, labels, symbols or icons.

Always refer to instruction 

manual

General warning - Important 

safety information

Hazardous voltage

Hot surfaces

IP65

Protection rating of 

equipment

   

Temperature range

 

Without isolation 

transformer

   Direct and alternating 

currents, respectively

  

Positive pole and negative 

pole of the input voltage 

(DC)

Always use safety clothing 

and/or personal safety 

devices

 

Point of connection for 

grounding protection

Time need to discharge 

stored energy

10

01

 Inverter model   

02

 Inverter Part Number

03

 Inverter Serial Number   

04

 Week/Year of manufacture

PVI-X.X-TL-OUTD-Y

P/N:PPPPPPPPPPP

WO:XXXXXXX

SO:SXXXXXXXX Q1

SN:YYWWSSSSSS WK:WWYY 

01

02

04

03

The models of inverter to which this guide refers are available in 3 power ratings: 3.0 kW, 3.6 kW and 4.2 kW.

The only difference in terms of components between the three power levels is the number of input connectors: 2 pairs in PVI-3.0/3.6-TL-OUTD models; 3 (2x MPPT1 

and 1x MPPT2) pairs in PVI-4.2-TL-OUTD models. Two types are available for each model: Standard or with DC disconnect switch (Version -S).

STANDARD VERSION

- S VERSION

01

03

02

04

05

06

07

08

17

18

19

20

15

09

10

11

12

13

14

17

16

18

19

20

15

09

10

11

12

13

14

UNO

POWER

ALARM

GFI

ESC

UP

DOWN

ENTER

Main components

01

Bracket

05

Front cover

09

DC Input terminal block

13

Signal terminal block

17

Input connectors (MPPT1)

02

Locking screw

06

LED Panel

10

AC Output terminal block

14

RJ45 Connectors

18

Input connectors (MPPT2)

03

Heat sink

07

Display

11

Channel configuration switch

15

RS485 line termination switch

19

AC cable gland

04

DSP Reprogramming 

connectors

08

Keyboard

12

Internal battery

16

DC Disconnect switch

20

Service cable glands

Available components

Quantity

Bracket for wall mounting

1

Bolts and screws for wall mounting

2 + 2

M6x10 screw

1

D.18 Washer

3

L-key, TORX TX20

1

M20 Cable gland

1

M25 Cable gland

1

Available components

Quantity

Two-hole gasket for M20 signal cable 

glands and cap TGM58

1 + 1

Jumpers for configuration of the 

parallel input channels

2

Connector for the connection of the 

communication and control signals

2

Male quick fit connectors

2 (3.0/3.6 kW)

3 (4.2 kW)

Female quick fit connectors

2 (3.0/3.6 kW)

3 (4.2 kW)

In additio

n to what 

is explain

ed in this

 guide, th

e safety a

nd installa

tion inform

ation pro

vided in th

e installat

ion manu

al must be

 read and

 followed

.

The techn

ical docu

mentation

 and the in

terface an

d manage

ment softw

are for th

e product

 are availa

ble at the

 website.

XXXXXXX

XXXX

XXXXXXXX

XXXXXXX

XXXXX

XXXXXXX

ABB solar

 inverter

s

Technical documentations

1

Transport and handling

Transport of the equipment, especially by road, must be carried out with by suitable ways and means for protecting the 

components from violent shocks, humidity, vibration, etc.

Lifting

The means used for lifting must be suitable to bear the weight of the equipment.

Unpacking and checking

The components of the packaging must be disposed on in accordance with the regulations in force in the country of 

installation.

When you open the package, check that the equipment is undamaged and make sure all the components are present. 

If you find any defects or damage, stop unpacking and consult the carrier, and also promptly inform the Service ABB.

Equipment weight

Model

Mass weight

PVI-3.0-TL-OUTD

PVI-3.0-TL-OUTD-S

PVI-3.6-TL-OUTD

PVI-3.6-TL-OUTD-S

PVI-4.2-TL-OUTD

PVI-4.2-TL-OUTD-S

17.5 Kg

UNO

POWER

ALARM

GFI

ESC

UP

DOWN

ENTER

Environmental checks

 -Consult the technical data to check the environmental parameters to be observed 

 -Installation of the unit in a location exposed to direct sunlight must be avoided as it may cause:

1. power limitation phenomena in the inverter (with a resulting decreased energy production by the system)

2. premature wear of the electrical/electromechanical components

3. premature wear of the mechanical components (gaskets) and of the user interface (display)

 -Do not install in small closed rooms where air cannot circulate freely

 -

To avoid overheating, always make sure the flow of air around the inverter is not blocked

 -

Do not install in places where gases or flammable substances may be present

 -Do not install in rooms where people live or where the prolonged presence of people or animals is expected, 

because of the noise (about 50dB(A) at 1 m) that the inverter makes during operation

Installations above 2000 metres

On account of the rarefaction of the air (at high altitudes), particular conditions may occur:

 -

Less efficient cooling and therefore a greater likelihood of the device going into derating because of high internal 

temperatures

 -Reduction in the dielectric resistance of the air that, in the presence of high operating voltages (DC input), can 

create electric arcs (discharges) that can reach the point of damaging the inverter

All installations at altitudes of over 2000 metres must be assessed case by case with the ABB Service 

department.

Installation position

 -

Install on a wall or strong structure capable of bearing the weight of the equipment

 -Install in safe, easy to reach places

 -If possible, install at eye-level so that the display and status LEDs can be seen easily 

 -

Install at a height that considers the heaviness of the equipment

 -Install vertically with a maximum inclination of +/- 5°

 -Choose a place with enough space around the unit to permit easy installation and 

removal of the object from the mounting surfaces; comply with the indicated minimum 

distances

 -For a multiple installation, position the inverters side by side; if the space available does 

not allow this arrangement, position the inverters in a staggered arrangement as shown 

in the figure so that heat dissipation is not affected by other inverters

Final installation of the inverter must not compromise access to any disconnection 

devices that may be located externally.

Please refer to the warranty terms and conditions available on the website and 

evaluate any possible exclusion due to improper installation.

15

cm

20 

cm

10cm

10cm

All versions of the inverter are equipped with two input channels (therefore with double maximum power point tracker MPPT) independent of each other, 

which can however be connected in parallel using a single MPPT.

Configuration of independent channels (default configuration)

This configuration involves the use of the two input channels (MPPT) in 

independent mode.

This means that the jumpers between the two channels (positive and negative) 

of the DC input terminal block 

09

 must not be installed and the switch 

11

 

located on the main board must be set to “IND”.

Configuration of parallel-connected channels

This configuration uses the two input channels (MPPT) connected in parallel. This means that the jumpers between the two channels (positive and negative) 

of the DC input terminal block 

09

 must be installed and the switch 

11

 located on the main board must be set to “PAR”.

    

09

Wall/Pole mounting

During installation, do not place the inverter with its front facing towards the ground.

-

 Position the bracket 

01

 so that it is perfectly level on the wall and use it as a boring template.

Make the 2 holes required, using a drill with a 10 mm diameter bit. The depth of the holes should be about 

70 mm. On the bracket 

01

 there are 5 holes with which to secure it: just 2 are enough to support the inverter if 

installed on stable, robust supports.

Secure the bracket to the wall 

B

 or to the pole 

A

 with the no. 2 10 mm wall plugs supplied with it (Step 

1). Check the stability of the bracket and if necessary use all the fixing points (5) there are on the bracket

Hook the inverter to the bracket spring corresponding with the insertion point in the bracket on the back of 

the inverter (Step 2).

Proceed to anchor the inverter to the bracket 

01

 by tightening the locking screw 

02

 located on the lower 

side (Step 3).

Unscrew the 4 screws and open the front cover 

05

 in order to make all the necessary connections.

Once the connections have been made, close the cover by tightening the 4 screws on the front to a 

minimum tightening torque of 1.5 Nm.

A

B

UNO

POWE

R

ALARM

GFI

ESC

UP

DOWN

ENTER

1

3

2

11

11

Reviews: