STARTING UP AND PROGRAMMING
52
Installation Manual
4
CHECKING THE IMPACT THRUST
The control board must be programmed to
respect the values indicated in Standard EN
12453:2000. All measurements must be made in
line with the method described in Standard EN
12445:2000.
• The Standard indicates that dynamic force
must be less than 400N.
Measure the impact thrust
and compare it to the
values indicated in Standard EN12453:2000. If the
values measured are higher than those in the Standard,
reduce the maximum thrust, the speed of the door, the
slow down speed, or increase the slow down distance.
Door speed:
A20X
Slowdown speed:
A30X
Slowdown distance:
A40X
Maximum thrust in opening:
A6-X
Maximum thrust in closing:
A6X-
5
FINAL CHECKS
Following installation and programming, start up the
system and check the devices installed.
1
Check the correct working of the key devices
(pushbutton and wall key, radio control).
2
Check the correct operation of the safety devices
(photocells or mechanical strips).
3
Place an obstacle and make the door collide with it
in order to check operation in the event of collision.
If the system does not work correctly, find out
why and put it right (see section “Failure
diagnosis” on page 53).
User instruction
1
Instruct the user with regards to the use and
maintenance of the installation and provide him/her
with the instructions on use.
2
Signpost the door, showing that it opens
automatically and indicating how to operate it
manually. Where appropriate, indicate that
operation is using the radio transmitter.