DM16-01.01.22en Mission
Inverter
Service manual
57
11.2.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0)
Error Code
P0
Malfunction decision
conditions
When the voltage signal that IPM send to compressor drive chip
is abnormal, the display LED will show “P0” and AC will turn off.
Supposed causes
●
Wiring mistake
●
IPM malfunction
●
Outdoor fan ass’y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Trouble shooting:
I
PM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red (-)Black
∞
(Several M
Ω
)
(+)Red (-)Black
∞
(Several M
Ω
)
P
N U
N
U V
V W
W (+)Red
Содержание Mission Inverter Series