29
The auto fan:
8.4.2.4 Evaporator low temperature T2 protection.
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and outdoor
fan will shut off.
When T2 is higher than TE6, the compressor and outdoor fan will restart up.
While TE5=4°C TE6=10°C for
,
ACP-09CH25AEF, ACP-09CH25AEG, ACP-12CH35AEF,
8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
Everytime the compressors start up, they will keep running for
+
t minutes(protections are active) and
then follow the below rules. (While
+
t=7.)
When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is
lower than Tk, the compressor and outdoor fan will start up.
ACP-12CH35AEG models.
While TE5=3°C TE6=14°C for
,
ACP-18CH50AEF, ACP-18CH50AEG models.
Tj=Ts+3 Tk=Ts+2.
文件使用
"pdfFactory Pro"
试用版本创建
www.fineprint.cn
Содержание ACP-09CH25AEF
Страница 2: ......
Страница 12: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2 PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 15: ...12 4 Refrigerant Cycle Diagram PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 17: ...14 ACP 09CH25AEF ACP 12CH35AEF ACP 09CH25AEG ACP 12CH35AEG PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 18: ...15 ACP 18CH50AEF ACP 18CH50AEG ACP 24CH70AEG ...
Страница 42: ......
Страница 43: ......
Страница 44: ......