26
8.3 Main Protection
8.3.1 Time Delay at restart for compressor.
8.3.2 Fan Speed is out of control.
----When Indoor Fan Speed keeps too low or too high for certain time, the unit will stop and the LED
will display the failure
8.3.3 Current protection
I3SEC
I5MIN
A
B
C
Resume
IFAN
IRESTORE
A zone : The current exceeds I
3SEC
for 5 seconds, the compressor and outdoor fan will shut off.
B zone: The current exceeds I
5min
for 5 minutes, the compressor and outdoor fan will shut off.
C zone: The current exceeds I
FAN
, the outdoor fan will shut off if AC is in heating mode.If AC is in
cooling mode, the indoor fan will run at low speed.
I
3SEC
=10.0A, I
5min
=8.5A, I
FAN
=6.5A, I
RESTORE
=5.5A for
ACP-09CH25AEF, ACP-09CH25AEG models.
I
3SEC
=12.0A, I
5min
=10.0A, I
FAN
=9.0A, I
RESTORE
=8.0A for
ACP-12CH35AEF, ACP-12CH35AEG models.
I
3SEC
=16.0A, I
5min
=15.0A, I
FAN
=14.0A, I
RESTORE
=12.0A for
ACP-18CH50AEF, ACP-18CH50AEG models.
8.3.4 Zero crossing detection error protetion
If AC can not detect zero crossing signal for 4 minutes or the zero crossing signal time interval is not
correct, the unit will stop and the LED will display the failure. The correct zero crossing signal time
interval should be between 6-13ms.
Содержание ACP-09CH25AEF
Страница 2: ......
Страница 12: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2 PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 15: ...12 4 Refrigerant Cycle Diagram PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 17: ...14 ACP 09CH25AEF ACP 12CH35AEF ACP 09CH25AEG ACP 12CH35AEG PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 18: ...15 ACP 18CH50AEF ACP 18CH50AEG ACP 24CH70AEG ...
Страница 42: ......
Страница 43: ......
Страница 44: ......