A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
142
9 Charge
refrigerant
through liquid
valve
Recharge the refrigerant to
the system through liquid
valve.
The charge volume must be
identical to the indications on
nameplate.
Disassembly and Assembly of 4-way valve
Remark : Before removing the 4-way valve, make sure that there is no refrigerant inside the pipe system and
that the power has been cut off.
Step Illustration
Handling
Instruction
1. Loosen the solenoid
valve
a. Cut off the power
supply
b. Recover the
refrigerant.
c. Loosen the bolts on
the solenoid valve
with a wrench
2. Remove the
solenoid valve
Remove the solenoid
away from the
four-way valve.
3. Remove the 4-way
valve
Use gas welding to
heat the pipes
connected on the four
opennings of 4-way
valve. Then, pull them
out from 4-way valve.
Before welding 4-way
valve, please record
the orientation of
4-way valve and
installing position of
each opening.
Содержание ACP-12CC35GECI
Страница 2: ......
Страница 3: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT ...
Страница 15: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL ...
Страница 16: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 23 CONTROL 1 OPERATION FLOWCHART 1 1Cooling Dry Operation ...
Страница 17: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation ...
Страница 52: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions ...
Страница 53: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION ...
Страница 76: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE ...
Страница 95: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection ...
Страница 96: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection ...
Страница 97: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection ...
Страница 98: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor ...
Страница 99: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection ...
Страница 100: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping ...
Страница 172: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 224 Model ACP 24CC70GECI ACP 24CF70GECI Exploded View ...
Страница 176: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 242 Model ACP 12CC35GECI Exploded View ...
Страница 178: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model ACP 18CC50GECI Exploded View ...
Страница 182: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 249 Model ACP 36CC100GECI Exploded View ...
Страница 188: ......
Страница 189: ......
Страница 190: ......