Engine's running procedure:
1. Start the engine and let it run at idle for 10 minutes. Stop the engine and
allow it to become completely cool. This procedure must be repeated 5
times.
2. Start the engine and let it run at idle for 60 minutes. Stop the engine and
allow it to become completely cool.
3. The first 25 hours of operation of the device, the load should not exceed
50% of the nominal figure. The work should be carried out by stages. Each
stage should not exceed 3 hours.
4. After 25 hours of the device's operation, replace the oil, after washing the
engine. Fill the generator with 1.65 liters of oil and run the engine for 10
minutes. Drain flushing oil, wash the oil filter and fill with new oil. Use for
cleaning the oil according to the ambient temperature.
BEFORE CONNECTING THE ELECTRIC CONSUMER
џ
Ensure that electrical appliances which are connected to the generator,
are intact and free of defects. Because there can be an electric shock or
fire;
џ
Make sure that the total power consumption of all connected electrical
appliances do not exceed the rated output power;
џ
The operation time of the generator between nominal and maximum power
should not exceed 5 minutes. Otherwise, this could lead to product failure;
џ
If you are using an extension cord, make sure that it is completely
unwound, and cable cross-section corresponds to the connected load. If
an extension cord or a cable has insufficient wire size, it can lead to voltage
drops, cable overheating and instability operation of connected
consumers;
џ
Do not overload electrical outlets of the generator. Each outlet has that
power, for which it is made. Try to distribute the load evenly between the
power outlets. The maximum current carrying capacity of a single electrical
outlet power must not exceed 16 A.
CALCULATION OF LOAD AND CONNECTION
Connect only single-phased power consumers with an operating voltage
of 230V ± 20% and frequency of 50 Hz to generator's ERS 4.6d and ERS 4.6dt
models.
The rules for calculating the load
1. Starting power of the connected to the generator unit with the highest inrush
current does not exceed the maximum capacity of the generator's product.
2. The total power consumption of all devices (with reactive and active loads)
must not exceed the rated capacity of the generator.
3. To calculate the correct load, you should consider the power factor of the
device.
4. There should be a 20% of power margin for proper and safe operation of the
diesel generator.
5. The power of connected consumers must not exceed the maximum power
socket of generator.
WARNING
!
Do not connect the product with the electrical power
consumers, which power exceeds the maximum capacity of
the device.
NOTE
!
Many appliances have the so-called inrush current, which
briefly increases the power consumption of electrical
appliances in several times. On this basis, to supply the power
consumers they must get the necessary power to run. Starting
capacity of such devices shall not exceed the maximum
capacity of this generator. The user, who has the highest
starting power, should be connected first to the device.