Product Specifications 

 

Electrical 

 

Power Requirements 

12VDC (Normal), 10.8VDC (Min.), 15VDC (Max) 

Output Power 

12VDC, 500mA (Max) 

Circuit Board

 

 

Device Interfaces 

1 - four position terminal block RS-485 data bus & power; 11 - three-position removable terminal blocks; 1 two 
position output terminal block; 4 - Relay Outputs/LEDs; 1 - Power LED; 1 - Status LED 
 

Outputs 

4 Relays NO/NC contact; 1 Siren output (sink), 1 Strobe output (sink) 

Input 

12 Inputs 

Buzzer  

Beeps intermittently (in a sequence of 1 second ON, 1 second OFF) when the Installer is locating the ioXpander-
12x4 Module (in the "Find Me" Menu). 

LED Status Indicators

 

Green: Power LED  - Lights continuously when powered 
Red: When the ioXpander-12x4 Module is connected, registered, and communicating with the ioXpander-8 the 
red LED is off. Otherwise, it blinks every second. 

Tamper Protection 

Open Double Tamper front and rear, if either breaks alarm will activate. 

Power Relays 

SRU-S-112L (TV-5); 12 VDC, 8A or 24 VDC, 4A 

RS-485 Bus

 

 

Data  Rate 

230Kbit/sec 

Bus Backbone 

26AWG  (Cat 5) 

DC 

< 22 AWG   

Bus Length 

500M/1640Ft: Max. 

Termination 

100 Ohm Termination: The RS-485 Bus needs to be terminated at both ends with a 100 Ohm resistor  

Operating 
Environment

 

 

 

Temp: -10°C to 70°C (14°F to 159°F) Humidity: 20% to 80%, non-condensing 

Physical

 

 

Weight 

670 grams (23.57 ounces) 

Construction 

ABS plastic 

Dimensions (H x W x 
D) 

230 x 199 x 47mm (90.625 x 7.83 x 1.84 inches) 

Regulatory 

EN 50131-3 Grade  2, Class II  

Warranty 

1-year limited warranty 

Product offerings and specifications are subject to change without notice. 

 

Important Shipment Information: 

The ioXpander-12x4 Module PGM Terminal Blocks are labeled in two different ways. There is no difference in 

their functionality. The only difference is how the PGM

’s PCBs are labeled.

 

 

 

 

 

W.E.E.E. Product Recycling Declaration

 

For  information regarding the recycling  of this product  you must contact the  company from which you orignially purchased it. 
If you are discarding this product and not returning it for repair then you must ensure that it is returned as identified by your supplier

This product is not to be thrown away with everyday waste - Directive 2002/96/EC Waste Electrical and Electronic Equipment.

 

Содержание ioXpander

Страница 1: ...back cover tamper switches for improved tamper protection RS 485 bus to communicate with the panel The ioXpander 12x4 Module is supported by the PowerMaster 33 E G2 only 1 1 Terminology Abbreviation Definition NO NC Normally Open Normally Closed EOL DEOL End of Line Double EOL HW Zone Hard wired zone ioXpander 8 Expander and bus controller on the PowerMaster 33 E G2 PGM Programmable Relay Output P...

Страница 2: ...fingers in the opening grove of each side and the push the cover upward 3 Remove the securing screw and push the tab to release the PCB with the interface 2 Release the protective cover snap and remove the cover 4 Knockouts provide cable accessibility when mounting on gang boxes or over hollow panels Use a cutter or screwdriver to open knockouts Insert screws through rear cover into the wall or ce...

Страница 3: ...tion there is one on each side of the box and thread the wires through the holes Wrap any excess wire around the PCB 7 Assemble the protective cover by placing it over the interface and snapping it into place 6 Snap the PCB back into place and make sure the tamper cap is in place Thread the cables inside the box through the cable cavities and connect as needed to the terminal blocks 8 Place the to...

Страница 4: ... shown in the tables below NC If the Wiring Type is End of Line If Wiring Type is NC If Wiring Type is NO Condition Zone Resistance Tamper Short Circuit 0 1 76 kΩ Normal 1 77 kΩ 2 64 kΩ Tamper 2 65 kΩ 3 52 kΩ Alarm 3 53 kΩ 5 26Ω Tamper Open Circuit 5 27 kΩ oc When there is NO ALARM the Panel detects 2 2K ohm between Zx and GND When there is ALARM the Panel detects 4 4K ohm between Zx and GND When ...

Страница 5: ... The installer needs to enroll each PGM output to the required output pin of the required ioXpander 12x4 Module For more information refer to section 6 Enrollment Process 4 3 Siren and Strobe Outputs The ioXpander 12x4 Module has built in Siren and Strobe outputs There is NO NEED TO ENROLL these outputs The Siren and Strobe outputs automatically activate when their functions are enabled in the Pow...

Страница 6: ... configuration Use only a power supply that is safety approved for IEC EN 60950 1 as a limited power source LPS with a rated voltage of 12Vdc and rated current of __1__a max Both the CP and PS that are used for powering the ioXpander 12x4 Module must be EN 50131 6 certified The loads that can connect to the relay outputs must be limited to a maximum of 12 VDC 8A or 24 VDC 4A Example of ioXpander 1...

Страница 7: ...www visonic com Page 7 of 11 D 306783 ioXpander 12x4 Module Rev 2 11 17 5 3 ioXpander 12x4 Module Circuit Board ...

Страница 8: ...der 12x4 Module s back casing and press OK The following is displayed ID ACCEPTED E0x Expander IOV ID NO 441 xxxx After connecting the ioXpander 12x4 Module to the PowerMaster 33 E G2 and exiting the Installer Mode the ioXpander 12x4 Module enrolls into the system 6 5 Step 5 optional to change a specific ioXpander 12x4 Module s ID Select the desired ioXpander 12x4 Module number E01 E04 and press O...

Страница 9: ... associated attached to PGM Output Pxx Note The PGM Output has no Device Settings that need programming The Installer may configure the PGM Outputs in the Menu 05 OUTPUTS PGM OUTPUTS PGM on HwExpndrs E0x Expander IOV Pxx PGM PIN 0y for more information consult the KP 250 PG2 Installer Guide 6 8 Cautions If an enrolled ioXpander 12x4 Module does NOT communicate with the PowerMaster 33 E G2 whether ...

Страница 10: ...4A RS 485 Bus Data Rate 230Kbit sec Bus Backbone 26AWG Cat 5 DC 22 AWG Bus Length 500M 1640Ft Max Termination 100 Ohm Termination The RS 485 Bus needs to be terminated at both ends with a 100 Ohm resistor Operating Environment Temp 10 C to 70 C 14 F to 159 F Humidity 20 to 80 non condensing Physical Weight 670 grams 23 57 ounces Construction ABS plastic Dimensions H x W x D 230 x 199 x 47mm 90 625...

Страница 11: ...ADVISED OF THE POSSIBILITY OF SUCH DAMAGE THE MANUFACTURER SHALL HAVE NO LIABILITY FOR ANY DEATH PERSONAL AND OR BODILY INJURY AND OR DAMAGE TO PROPERTY OR OTHER LOSS WHETHER DIRECT INDIRECT INCIDENTAL CONSEQUENTIAL OR OTHERWISE BASED ON A CLAIM THAT THE PRODUCT FAILED TO FUNCTION HOWEVER IF THE MANUFACTURER IS HELD LIABLE WHETHER DIRECTLY OR INDIRECTLY FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LI...

Отзывы: