Visonic Fully supervised wireless accessories Скачать руководство пользователя страница 10

SMD-426, SMD-427 

D-302758 

3.2 Where to Install Smoke Detectors 

Smoke detectors should be installed in accordance with 

the NFPA Standard 74 (National Fire Protection 

Association, Batterymarch Park, Quincy, MA 02169). For 

complete coverage in residential units, smoke detectors 

should be installed in all rooms, halls, storage areas, 

basements and attics in each family living unit. Minimum 

coverage is one detector on each floor and one in each 

sleeping area and attics in each family living unit. For 

maximum protection, a smoke detector should be located 

outside primary sleeping areas or on each level of your 

home. Here are a few useful tips for you: 

 Install a smoke detector in the hallway outside every 

separate bedroom area, as in Figure 5. Two detectors are 

required in homes with two bedroom areas, as in Figure 6. 

 Install a smoke detector on every floor of a multi-floor 

home or apartment, as shown in Figure 7. 

  Install a minimum of two detectors in any household. 

  Install a smoke detector inside every bedroom. 

  Install smoke detectors at both ends of a bedroom hallway if 

the hallway is more than 12 meters (40 feet) long. 

 

Figure 5. 

Locations for Placing Smoke Detectors in a Single 

Residence with only One Sleeping Area

 

 Install a smoke detector inside every room where one 

sleeps with the door partly or completely closed, since 

smoke could be blocked by the closed door and a hallway 

alarm may not wake up the sleeper if the door is closed. 

 

Figure 6.

 Locations for Placing Smoke Detectors in Single-

Floor Residence with More than One Sleeping Area. 

 

Figure 7. 

Placing Smoke Detectors in a Multi-Floor 

Residence 

 Install basement detectors at the bottom of the basement 

stairwell. 

 Install second-floor detectors at the top of the first-to-

second floor stairwell. 

 Be sure no door or other obstruction blocks the path of 

smoke to the detector. 

 Install additional detectors in your living room, dining 

room, family room, attic, utility and storage rooms. 

 Install smoke detectors as close to the center of the 

ceiling as possible. If this is not practical, put the 

detector on the ceiling, at least 10 cm (4 inches) away 

from any wall or corner, as shown in Figure 8. 

 If ceiling mounting is not possible and wall mounting is 

permitted by your local and state codes, locate the 

detectors between 10 - 15 cm (4 - 6 inches) from the 

ceiling, also see Figure 8. 

 If some of your rooms have sloped, peaked, or gabled 

ceilings, try to mount detectors 0.9 meter (3 feet) 

measured horizontally from the highest point of the 

ceiling as shown in Figure 9. 

 

Figure 8.

 Recommended Best 

and Acceptable Locations to 

Mount Smoke Detectors

 

 

 

Figure 9. 

Recommended 

Location to Mount Smoke 

Detectors in Rooms with 

Sloped, Gabled or 

Peaked Ceiling

 

 

CAUTION

 (As required by the California State 

Fire Marshall) 
"Early warning fire detection is best achieved by 
the installation of fire detection equipment in all 
rooms and areas of the household as follows:

 

(1) A smoke detector installed in each separate sleeping 
area (in the vicinity, but outside the bedrooms), and (2) 
Heat or smoke detectors in the living rooms, dining rooms, 
bedrooms, kitchens, hallways, attics, furnace rooms, 
closets, utility and storage rooms, basements and attached 
garages." 

3.3 Where Not to Install Smoke Detectors  

False alarms occur when smoke detectors are installed 
where they will not work properly. To avoid false alarms, 
do not install smoke detectors in the following situations: 

 Combustion particles are by-products of something 

burning. Do not install smoke detectors in or near areas 
where combustion particles are present, such as 
kitchens with few windows or poor ventilation, garages 
where there may be vehicle exhaust, near furnaces, hot 
water heaters and space heaters. 

 Do not install smoke detectors less than 6 meters (20 

feet) away from places where combustion particles are 
normally present, like kitchens. If a 20-foot distance is 
not possible, try to install the detector as far away from 
the combustion particles as possible, preferably on the 
wall. To prevent false alarms, provide good ventilation in 
such places. 

IMPORTANT:

 

Never try to avoid false alarms by 

disabling the detector. 

 Do not mount smoke detectors in the path of fresh air 

intake. The flow of fresh air in and out can drive smoke 

away from the smoke detector; thus reducing its 

efficiency. Figure 10 indicates the correct and incorrect 

locations concerning this problem. 

  Near paint thinner fumes. 

Содержание Fully supervised wireless accessories

Страница 1: ...Accessories Guide Fully supervised wireless accessories for PowerMax systems ...

Страница 2: ... SETTINGS 11 6 SMOKE DETECTOR TEST 12 6 1 Diagnostics Test 12 7 MOUNTING 13 8 SMOKE DETECTOR LIMITATIONS 13 9 TAKING CARE OF THE SMD 426 or SMD 427 13 9 1 Battery Replacement 13 9 2 Maintenance 14 10 ADDITIONAL ADVICE 14 10 1 Routine Testing 14 10 2 Tips to Enhance Your Protection From Fires 14 10 3 More Tips on How to Face a Fire at Home 15 11 STATEMENTS OF COMPLIANCE 15 CONTACT SENSORS MC 302 PG...

Страница 3: ... replaced by an incorrect type Dispose of used battery according to manufacturer s instructions Battery Life Expectancy 8 years for typical use Note If transmission is still possible despite the battery condition the unit will send a low battery signal to the control panel Transmitted Messages Arm Away Arm Home Arm Latchkey Disarm AUX and Panic Operating Temperature 0 to 55 C 32 to 131 F Dimension...

Страница 4: ... with the screw 3 2 Figure 3 Battery Replacement 6 2 Cleaning The keyfob may get dirty if touched with greasy fingers Clean it only with a soft cloth or sponge moistened lightly with a mixture of water and mild detergent and wipe it dry immediately The use of abrasives of any kind is strictly forbidden Also never use solvents such as kerosene acetone or thinner 7 TESTING A NEW UNIT Since the KF 23...

Страница 5: ...0m 32 8ft 10m 32 8ft HORIZONTAL VIEW VERTICAL VIEW NEXT PG2 0 5 4m NEXT K9 PG2 2 4m Fig 2 Coverage Pattern Walk test ELECTRICAL Internal Battery 3V Lithium battery type CR 123A or equivalent Note For UL installations use Panasonic Sanyo GP or Varta only Use only the above battery Dispose of used battery according to the manufacturer s instructions Operating Voltage 2 5 3 3V Nominal Battery Capacit...

Страница 6: ... Press the or button to select between LOW sensitive and HIGH sensitive for example HIGH sensitive or 8 Press OK I to confirm the selection The PowerMax10 G2 display will revert to Event counter OK I 9 Press the button The PowerMax10 G2 display will read DISARM Activity 10 Press the OK I button The PowerMax10 G2 display will read NOT Active OK I 11 Press the or button repeatedly to select between ...

Страница 7: ...kes place below 1 m 3 ft Above the 1 m 3 ft height limit the detector is immune to 19 kg 42 lb pets but the pet immunity will decrease as the pet gets closer to the detector It is therefore recommended to select a mounting location that minimizes potential close proximity of animals 1 2 Push catch and remove board On surface In corner 3 Insert battery Front Tamper switch Back Tamper switch Release...

Страница 8: ...nce by one or more of the following measures Re orient or re locate the receiving antenna Increase the distance between the device and the receiver Connect the device to an outlet on a circuit different from the one that supplies power to the receiver Consult the dealer or an experienced radio TV technician WARNING Changes or modifications to this unit not expressly approved by the party responsib...

Страница 9: ...t is reported once Tamper restore is reported when the tamper switch is restored ALARM REPORT In the alarm condition the detector sends the alarm event to the control panel When the alarm condition is restored the detector sends an alarm restore event to the control panel and sets the alarm restore indication red LED blinks once per sec Note The alarm restore indication can be cleared via the cont...

Страница 10: ...cm 4 inches away from any wall or corner as shown in Figure 8 If ceiling mounting is not possible and wall mounting is permitted by your local and state codes locate the detectors between 10 15 cm 4 6 inches from the ceiling also see Figure 8 If some of your rooms have sloped peaked or gabled ceilings try to mount detectors 0 9 meter 3 feet measured horizontally from the highest point of the ceili...

Страница 11: ...lert Figure 10 Recommended Smoke Detector Locations to Avoid Air Streams with Combustion Particles WARNING Never remove batteries to stop a false alarm Open a window or fan the air around the detector to get rid of the smoke The alarm will turn itself off when the smoke is gone If false alarms persist attempt to clean the detector as described in this manual WARNING Do not stand close to the detec...

Страница 12: ...ent which will be reported by the transceiver to the control panel 4 ENROLLMENT Refer to the PowerMax10 G2 Installer Guide for the device enrollment procedure 5 MODIFY DEVICE SETTINGS This section describes how to configure the parameters of the smoke detector from the PowerMax10 G2 control panel To Modify the Smoke Detector Device Settings Refer to the PowerMax10 G2 Installer Guide and perform th...

Страница 13: ... that need to be updated as follows DEV UPDATING NNN For detailed instructions on ADDING DEVICES DELETING DEVICES and MODIFYING DEVICES see the PowerMax10 G2 Installer Guide 6 SMOKE DETECTOR TEST Enter the test mode by pressing the test button for 2 seconds and release it In this mode the detector will test smoke heat and battery functions If all functions are good the red LED lights 0 5s off 0 5s...

Страница 14: ...or alcohol may not hear the alarm or be able to react to it Therefore locate this smoke detector which has a sounder rated at 85 dB at 10 feet on every level in every sleeping area and in every bedroom of the household E This detector if used as a stand alone unit will not alert people who are hard of hearing F In general detectors may not always warn you about fires caused by carelessness and saf...

Страница 15: ...d immediately If the alarm horn begins to beep once every 30 sec for further details see par 3 2 this signal means that the detector s battery is weak Install a new battery immediately Keep fresh batteries on hand for this purpose 10 2 Tips to Enhance Your Protection From Fires Putting up smoke detectors is only one step in protecting your family from fires You must also reduce the chances of fire...

Страница 16: ...ct to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment The digital circuit of this device h...

Страница 17: ...nd RSS 210 of Industry and Science Canada Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This device complies with the essential requirements and provisions of Directive 1999 5 EC of the European Parliament and of the Council of 9 ...

Страница 18: ...ller Guide 6 LOCAL DIAGNOSTICS TEST Before testing separate the base from the cover see Fig 3a A Press the tamper switch once and release it B Put back the cover to return the tamper switch to its normal undisturbed position and then secure the front cover to the base with the case closure screw C Momentarily open the door or window and verify the red LED blinks indicating detection D After 2 seco...

Страница 19: ...ularly to determine whether there are sources of interference and to protect against faults The user is cautioned that changes or modifications to the unit not expressly approved by Visonic Ltd could void the user s FCC or other authority to operate the equipment ...

Страница 20: ...Current drain at 5 7 VDC Frequency MHz 433 868 915 100 mA 100 mA 100 mA Battery Backup Duration with fully charged 1300 mA h battery 48 hours LED indicator Green LED lights when AC power on Compliance with Standards Europe EN 50131 1 EN 50130 5 EN 50131 6 EN 301489 EN 50130 4 EN 300 220 USA FCC CFR47 Part 15 Canada RSS210 Operating Temperature 0 C to 49 C 32 F to 120 F Dimensions H x W x D 161x161...

Страница 21: ... button once and release it The red LED and then the green LED will switch ON and then OFF in turn to indicate that the repeater is now fully operational B After 2 seconds the LED blinks 3 times The following table indicates received signal strength indication LED response Reception Green LED blinks Strong Orange LED blinks Good Red LED blinks Poor No blinks No communication IMPORTANT Reliable rec...

Страница 22: ...harmful interference to radio and television reception However there is no guarantee that interference will not occur in a particular installation If this device does cause such interference which can be verified by turning the device off and on the user is encouraged to eliminate the interference by one or more of the following measures Re orient or re locate the receiving antenna Increase the di...

Страница 23: ...lue amber or transparent lens according to the desired strobe light color Siren activity LED A flashing LED optional at the bottom of the siren front panel indicates siren activity can be disabled by the control panel Double Tamper protection When the siren front panel is removed or when the siren is removed from the wall tamper alarm is sent to the alarm system Fig 1a External View Fig 1b Mountin...

Страница 24: ...evice does cause such interference which can be verified by turning the device off and on the user is encouraged to eliminate the interference by one or more of the following measures Re orient or re locate the receiving antenna Increase the distance between the device and the receiver Connect the device to an outlet on a circuit different from the one which supplies power to the receiver Consult ...

Страница 25: ...NTRY Beeps 6 Press the OK I button The PowerMax10 G2 display will read Disabled OK I 7 Press the or button repeatedly to select between Disabled Disabled Home and Enabled for example Enabled or 8 Press OK I to confirm the selection The PowerMax10 G2 display will revert to EXIT ENTRY Beeps OK I 9 Press the button The PowerMax10 G2 display will read SQUAWK 10 Press the OK I button The PowerMax10 G2 ...

Страница 26: ...onnected to AC or 24 Press OK I to confirm the selection The PowerMax10 G2 display will revert to AC POWER Connect OK I 25 Press the button The PowerMax10 G2 display will read AUTO TAMPER ALRM 26 Press the OK I button The PowerMax10 G2 display will read Disabled OK I 27 Press the or button to select between Disabled and Enabled for example Enabled or 28 Press OK I to confirm the selection The Powe...

Страница 27: ...nd to indicate that the siren is now fully operational B After 2 seconds the LED blinks 3 times The following table indicates received signal strength indication LED response Reception Green LED blinks Strong Orange LED blinks Good Red LED blinks Poor No blinks No communication IMPORTANT Reliable reception must be assured Therefore poor signal strength is not acceptable If you receive a poor signa...

Страница 28: ...ON However if the Manufacturer is held liable whether directly or indirectly for any loss or damage arising under this limited warranty THE MANUFACTURER S MAXIMUM LIABILITY IF ANY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT which shall be fixed as liquidated damages and not as a penalty and shall be the complete and exclusive remedy against the Manufacturer When accepting the de...

Страница 29: ... CT 06002 1376 PHONE 860 243 0833 800 223 0020 FAX 860 242 8094 VISONIC LTD UK UNIT 6 MADINGLEY COURT CHIPPENHAM DRIVE KINGSTON MILTON KEYNES MK10 0BZ TEL 0870 7300800 FAX 0870 7300801 PRODUCT SUPPORT 0870 7300830 VISONIC GMBH D KIRCHFELDSTR 118 D 42015 DÜSSELDORF GERMANY FAX 0211 60069619 Email info dach visonic com VISONIC IBERICA ISLA DE PALMA 32 NAVE 7 POLÍGONO INDUSTRIAL NORTE 28700 SAN SEBAS...

Страница 30: ...ss accessories Fully supervised wireless accessories ully supervised wireless accessories Fully supervised wireless accessories Fully upervised wireless accessories Fully supervised wireless accessories Fully supervised wireless accessories Fully supervised wireless accessories Fully supervised wireless ccessories Fully supervised wireless accessories Fully supervised wireless accessories ully sup...

Отзывы: