Wiring 

  

 

  Do not touch live wires. 

 

  Install an external circuit breaker. Guard against short-circuiting in external wiring. 

  Use appropriate circuit protection devices. 

  Unused pins should not be connected. Ignoring this directive may damage the device. 

  Double-check all wiring before turning on the power supply. 

Caution

 

  To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 

  Do not use tin, solder, or any substance on stripped wire that might cause the wire  

strand to break. 

  Install at maximum distance from high-voltage cables and power equipment. 

 

Wiring Procedure 

Use crimp terminals for wiring; use 3.31 mm ² –0.13 mm² wire (12-16 AWG): 

1. Strip the wire to a length of 7±0.5mm (0.270–0.300“). 

2. Unscrew the terminal to its widest position before inserting a wire.  

3. Insert the wire completely into the terminal to ensure a proper connection. 

4. Tighten enough to keep the wire from pulling free. 

  Input or output cables should not be run through the same multi-core cable or share 

the same wire. 

  Allow for voltage drop and noise interference with I/O lines used over an extended distance.  

Use wire that is properly sized for the load. 

  The controller and I/O signals must be connected to the same 0V signal. 

     

   

I/Os 

 

V130/V350/V130J/V350J/V430J-TA24 models 

comprise a total 12 inputs, 10 digital outputs and 2 

analog outputs. 

 

Input functionality can be adapted as follows: 
 

All 12 inputs may be used as digital inputs. They may be wired in a group via a single jumper  
as either npn or pnp. 

 

In addition, according to jumper settings and appropriate wiring:  

-  Inputs 5 and 6 can function as either digital or analog inputs. 
-  Input 0 can function as a high-speed counter, as part of a shaft-encoder, or as a normal  

digital input. 

-  Input 1 can function as either a counter reset, normal digital input, or as part of a  

shaft-encoder. 

-  If input 0 is set as a high-speed counter (without reset), input 1 can function  

as a normal digital input. 

-  Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; Input 11 can also 

serve as the CM signal for PT100. 

 

Содержание OPLC V130-33-TA24

Страница 1: ...ad Yes None Function Keys None Yes Com Port Built in RS232 485 Yes Yes Yes Yes Yes USB device mini B None None None None Yes Com Ports separate order user installed The user may install a CANbus port...

Страница 2: ...irs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging t...

Страница 3: ...0J V350J 92x92 mm 3 622 x3 622 V430J 122 5x91 5 mm 4 82 x3 6 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the side...

Страница 4: ...nics V430J DIN rail Mounting V130 V350 V130J V350J 1 Snap the controller onto the DIN rail as shown in the figure to the right 2 When properly mounted the controller is squarely situated on the DIN ra...

Страница 5: ...r output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with I O lines used over an extended distance Use wire that is...

Страница 6: ...uts 7 8 Set Type Digital or RTD TC 1 Set to JP1 JP2 JP3 Digital A A A Thermocouple B B B PT100 B A B Inputs 9 10 Set Type Digital or RTD TC 0 Set to JP5 JP6 JP7 Digital A A A Thermocouple B B B PT100...

Страница 7: ...Vision OPLC Unitronics 7 I O Wiring npn sink Input Input wiring HSC input wiring pnp source Input Input wiring HSC input wiring Shaft encoder...

Страница 8: ...Brown Blue J 200 to 760 C 328 to 1400 F White Red Yellow Blue K 200 to 1250 C 328 to 2282 F Yellow Red Brown Blue N 200 to 1300 C 328 to 2372 F Orange Red Orange Blue R 0 to 1768 C 32 to 3214 F Black...

Страница 9: ...stem earth ground Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or...

Страница 10: ...ommunicate with serial devices and applications such as SCADA Use RS485 to create a multi drop network containing up to 32 devices Pinouts The pinouts below show the PLC port signals RS232 RS485 Contr...

Страница 11: ...RS485 network USB Port Caution The USB port is not isolated Make sure that the PC and the controller are grounded to same potential The USB port may be used for programming OS download and PC access...

Страница 12: ...screws Note that you must replace the back cover securely before powering up the controller The information in this document reflects products at the date of printing Unitronics reserves the right sub...

Отзывы: