Setting RS232/RS485 Communication Parameters, V430J 

This port may be set to either RS232 or RS485 via DIP switches:  

The table shows the DIP switches factory default settings. Use the table to adapt the settings.

 

 

Switch Settings 

 

RS232* 

ON 

OFF

 

OFF

 

ON

 

OFF

 

OFF 

RS485 

OFF 

ON

 

ON

 

OFF

 

OFF 

OFF

 

RS485 with 
termination** 

OFF

 

ON 

ON

 

OFF

 

ON

 

ON 

* Default factory setting

 

** Causes the unit to function as an end unit in an RS485 network

 

 

USB Port 

 

Caution

 

  The USB port is not isolated.  

Make sure that the PC and the controller are grounded to same potential. 

The USB port may be used for programming, OS download, and PC access. 

 

Setting RS232/RS485 Communication Parameters, V130/V350/V130J/V350J  

This port may be set to either RS232 or RS485 via jumper.  

 

The accompanying figure shows the jumper factory  
default settings. 

These jumpers may be used to: 

  Set communications to RS485, by setting both COMM  

jumpers to ‘485’. 

  Set RS485 termination, by setting both TERM jumpers 

to ‘OFF’. 

To access the jumpers, you must open the controller 
according to the instructions on page 12. 

Содержание OPLC V130-33-TA24

Страница 1: ...ad Yes None Function Keys None Yes Com Port Built in RS232 485 Yes Yes Yes Yes Yes USB device mini B None None None None Yes Com Ports separate order user installed The user may install a CANbus port...

Страница 2: ...irs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging t...

Страница 3: ...0J V350J 92x92 mm 3 622 x3 622 V430J 122 5x91 5 mm 4 82 x3 6 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the side...

Страница 4: ...nics V430J DIN rail Mounting V130 V350 V130J V350J 1 Snap the controller onto the DIN rail as shown in the figure to the right 2 When properly mounted the controller is squarely situated on the DIN ra...

Страница 5: ...r output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with I O lines used over an extended distance Use wire that is...

Страница 6: ...uts 7 8 Set Type Digital or RTD TC 1 Set to JP1 JP2 JP3 Digital A A A Thermocouple B B B PT100 B A B Inputs 9 10 Set Type Digital or RTD TC 0 Set to JP5 JP6 JP7 Digital A A A Thermocouple B B B PT100...

Страница 7: ...Vision OPLC Unitronics 7 I O Wiring npn sink Input Input wiring HSC input wiring pnp source Input Input wiring HSC input wiring Shaft encoder...

Страница 8: ...Brown Blue J 200 to 760 C 328 to 1400 F White Red Yellow Blue K 200 to 1250 C 328 to 2282 F Yellow Red Brown Blue N 200 to 1300 C 328 to 2372 F Orange Red Orange Blue R 0 to 1768 C 32 to 3214 F Black...

Страница 9: ...stem earth ground Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or...

Страница 10: ...ommunicate with serial devices and applications such as SCADA Use RS485 to create a multi drop network containing up to 32 devices Pinouts The pinouts below show the PLC port signals RS232 RS485 Contr...

Страница 11: ...RS485 network USB Port Caution The USB port is not isolated Make sure that the PC and the controller are grounded to same potential The USB port may be used for programming OS download and PC access...

Страница 12: ...screws Note that you must replace the back cover securely before powering up the controller The information in this document reflects products at the date of printing Unitronics reserves the right sub...

Отзывы: