Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 12.
Incompatible jumper settings and wiring connections may seriously damage the controller.
Digital Inputs 0-11: Set Type
Set to
JP12 (all Inputs)
npn (sink)
A
pnp (source)*
B
Inputs 7/8: Set Type - Digital or RTD/TC #1
Set to
JP1
JP2
JP3
Digital*
A
A
A
Thermocouple
B
B
B
PT100
B
A
B
Inputs 9/10: Set Type - Digital or RTD/TC #0
Set to
JP5
JP6
JP7
Digital*
A
A
A
Thermocouple
B
B
B
PT100
B
A
B
Input 11: Set Type - Digital or CM for PT100
Set to
JP11
Digital*
A
CM for PT100
B
Input 5: Set Type - Digital or Analog #3
Set to
JP4
JP10
Analog Output 0: Set to Voltage/Current
Digital*
A
A
Set to
JP13
Voltage
B
A
Voltage*
A
Current
B
B
Current
B
Input 6: Set Type - Digital or Analog #2
Set to
JP8
JP9
Analog Output 1: Set to Voltage/Current
Digital*
A
A
Set to
JP14
Voltage
B
A
Voltage*
A
Current
B
B
Current
B
*Default settings