Annex 1: EcoLite Current Configuration
WARNING
This is not user configurable and must be set by a qualified electrician / installer. Any changes to the maximum
advertised current of the unit need to be done with important consideration for other components and
infrastructure. Misuse of this could cause fire and injury.
On leaving the factory the default maximum charge level will be configured to the maximum rated
current as per the identification label on the unit.
If a different rating is required for the installation; the current configuration of the unit must be set to
match the installation requirements, and the identification label updated. Suitably rated protective
devices should be placed upstream and fitted in the unit and signed off by a qualified professional.
A minimum current setting of 12A on either EcoLite is required for SLS to operate correctly.
To change the current set the current configuration DIP switch (Fig. C - 8) as per the configuration
table below.
DIP switch position
1
2
3
4
Current Level
OFF OFF OFF OFF
32
ON OFF OFF OFF
6
OFF ON OFF OFF
9
ON ON OFF OFF
10
OFF OFF ON OFF
11
ON OFF ON OFF
14
OFF ON ON OFF
15
ON ON ON OFF
16
OFF OFF OFF ON
18
ON OFF OFF ON
20
OFF ON OFF ON
22
ON ON OFF ON
24
OFF OFF ON ON
25
ON OFF ON ON
28
OFF ON ON ON
30
ON ON ON ON
Demo mode