background image

Installation

9

Notes: 

1) The addition of chlorine (bleach) to a hot water tank that has in the past been fed with untreated raw water with 

high levels of other contaminants (iron, manganese, hydrogen sulphide, organics, etc.) will result in oxidation of 

these contaminants and may require repeated flushing of the hot water tank. This contingency must be dealt with 

independently under the start-up procedure for any other conditioners that may form a part of the pre-treatment for 

the UV unit.

2) The above cleaning procedure will result in a massive chlorine residual far in excess of the 0.5 to 1.0 mg/L 

typically present in municipally chlorinated water and of a magnitude consistent with the minimum 50 mg/L 

chlorine solution recommended for the cleaning of distribution systems known to be contaminated. Do not 

consume water until complete system has been flushed

.

1

•   

Ensure the controller is 

plugged in for entire cleaning 

process.

2

2

1

2

2

2

•   

Shut off the water supply.

•   

Close each faucet.

3

•   

Press the pressure button to 
release the pressure from the 
cartridges.

4

•   

Remove sump housing(s) 
using sump wrench.

5

      Household 5.25%
       Bleach Solution

BLEACH

x2

2

1

•   

Remove cartridge(s) and 
pour 2 cups of household 
bleach solution into the sump 
housing(s).

Note: 

DO NOT use 

Hydrogen Peroxide.

6

•   

Connect only the sump 
housing(s) to the unit.

7

•   

Open each faucets and turn 
on water supply.

•   

Allow water to fill the 
chamber.

8

0

30

15

45

30 mins

•   

Close all faucets and allow 
bleach to settle in the water 
lines for 30 minutes.

9

•   

With all faucets closed, 
remove sump housing(s) 
using sump wrench. 

10

10

1

2

•   

Reinstall the cartridge(s) into 
sump housing(s) and connect 
to the unit.

•   

Flush all water outlets until 
bleach can no longer be 
smelled (at least 5 minutes).

11

11

•   

Press the pressure button to 
purge air and to complete the 
cleaning procedure.

Содержание VT1

Страница 1: ...1 t 1 519 763 1032 tf 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail info viqua com www viqua com Models VT1 VT1 2 VT1 2A VT1 2B VT1 12 VT4 VT4 2 VT4 2A VT4 2B VT4 12 Owner s Manual Powered by 520074_RevV ...

Страница 2: ...ed VIQUA replacement lamps Use of widely available non genuine replacement lamps has been shown to damage the control module of VIQUA UV equipment An increasing number of calls to VIQUA Technical Support are connected with non genuine lamps being used unknowingly as replacements Damage arising from the use of non genuine lamps poses a safety risk and is not covered by equipment warranty Unless the...

Страница 3: ...it Interrupter GFCI This symbol indicates there is a potential for VERY hot water when flow is started DANGER Failure to follow these instructions will result in serious injury or death Electric Shock To avoid possible electric shock special care should be taken since water is present near the electrical equipment Unless a situation is encountered that is explicitly addressed by the provided maint...

Страница 4: ...If the lamp breaks then avoid inhalation or ingestion of the debris and avoid exposure to eyes and skin Never use a vacuum cleaner to clean up a broken lamp as this may scatter the spilled mercury Obey local regulations and guidelines for the removal and disposal of mercury waste NOTICE The UV lamp inside the UV system is rated at an effective life of approximately 9000 hours To ensure continuous ...

Страница 5: ...4 2B VT4 12 2 O ring 410867 Used on all systems 3 Hard glass coated Sterilume EX UV lamps for long consistent life 9000 hours S212RL VT1 VT1 2 VT1 2A VT1 2B VT1 12 S330RL VT4 VT4 2 VT4 2A VT4 2B VT4 12 4 Retaining nut RN 001 Used on all systems 5 Lamp connector 6 Controller BA VT VT1 and VT4 BA VT 2 VT1 2 and VT4 2 BA VT 2A VT1 2A and VT4 2A BA VT 2B VT1 2B and VT4 2B 7 Controller for 12VDC models...

Страница 6: ... causing a potential fire hazard Drip loops in all cordage connected to controller is highly recommended Refer to Figure 4 The complete water system including any pressure or hot water tanks must be sterilized before start up by flushing with chlorine household bleach to destroy any residual contamination The UV system is intended for indoor use only Do not install UV system where it may be expose...

Страница 7: ...it is required to install a GFCI make sure that this is taken into consideration prior to any installation Make sure you leave enough clearance above the system connector to facilitate lamp service a length equal to the length of the unit should suffice 3 Mount the system to the wall using the supplied clamps Various connection methods can be used to connect the water source to the system however ...

Страница 8: ...is from the O ring seal In case of a leak shut water off drain cell remove the retaining nut wipe the O ring and threads Clean and re install 7 Once it is determined that there are no leaks plug the system into the ground fault interrupter and check controller to ensure the system is operating properly The controller should illuminate without any alarms 8 Allow the water to run for a few minutes t...

Страница 9: ...o not consume water until complete system has been flushed 1 Ensure the controller is plugged in for entire cleaning process 2 2 1 2 2 2 Shut off the water supply Close each faucet 3 Press the pressure button to release the pressure from the cartridges 4 Remove sump housing s using sump wrench 5 Household 5 25 Bleach Solution BLEACH x2 2 1 Remove cartridge s and pour 2 cups of household bleach sol...

Страница 10: ...efer to www lamprecycle org for UV lamp disposal Do not use water during replacement of UV lamp 1 Shut off the water line to UV chamber and release system pressure before servicing 2 0 30 15 45 10 mins Disconnect main power source and allow the unit to cool for 10 minutes 3 1 2 Remove the lamp connector by squeezing the plastic locking tabs on the side of the connector 4 Hg UV Remove the UV lamp i...

Страница 11: ...e use of the water 1 Drain the UV chamber by using the drain port 2 1 2 3 Remove the bottom retaining nut floating spring and O ring 3 1 2 Remove the top retaining nut and O ring 4 Remove the quartz sleeve 5 Mild Acid Clean the quartz sleeve with a cloth soaked in CLR vinegar or some other mild acid and then rinse with water Note If sleeve cannot be completely cleaned or it is scratched or cracked...

Страница 12: ...5 lbs Electrical Voltage3 100 140 V 50 60 Hz 12 VDC 200 240 V 50 60 Hz 100 140 V 50 60 Hz 12 VDC 200 240 V 50 60 Hz Max Current 0 28 A 1 8 A 0 16 A 0 28 A 1 8 A 0 16 A Power Consumption 13 W 13 W 13 W 19 W 19 W 19 W Lamp Watts 9 W 9 W 9 W 15 W 15 W 15 W Maximum Operating Pressure 125 psi 861 kPa 125 psi 861 kPa 125 psi 861 kPa 125 psi 861 kPa Minimum Operating Pressure 5 psi 34 kPa 5 psi 34 kPa 5 ...

Страница 13: ...are components to be free from defects in material and workmanship for a period of three 3 years from the date of purchase During this time VIQUA will repair or replace at its option any defective parts covered by the warranty Please return the defective part to your dealer who will process your claim One Year Limited Warranty for UV lamps Sleeves and UV Sensors VIQUA warrants UV lamps sleeves and...

Страница 14: ...425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 tf 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail info viqua com www viqua com ...

Отзывы: