Installation
6
Section 3
Installation
3.1 UV System
The UV system is designed to be mounted either horizontally or vertically at the point-of-use or point-of-entry depending on
the specific flow rate of the unit.
If installing the chamber in horizontal position the outlet port must be pointing upwards to ensure all air is fully purged from
the chamber.
Note:
The ideal installation is vertical with the lamp connector on top. This is to prevent water damage from occurring on the
lamp pins and lamp connector.
•
The controller should be mounted either above or beside the UV chamber. Always mount controller horizontally to
prevent moisture from running down cordage and causing a potential fire hazard. Drip loops in all cordage connected to
controller is highly recommended. Refer to
.
•
The complete water system, including any pressure or hot water tanks, must be sterilized before start up by flushing
with chlorine (household bleach) to destroy any residual contamination.
•
The UV system is intended for indoor use only. Do not install UV system where it may be exposed to the weather.
•
Install the UV system on cold water line only.
•
A 5 micron sediment filter must precede the UV system. Ideally, the UV system should be the last stage the water
receives before it reaches the faucet.
C A U T I O N
Electronic controller must be connected to a Ground Fault Protected Circuit (GFCI) receptacle. Ensure green ground wire ring terminal is securely
fastened to ground stud on UV chamber.
Figure 2 Installation - Vertical and Horizontal
Vertical
Horizontal