Manual VIPA TM-E
Chapter 3
Deployment
HB39E - TME - RE_900-1E630 - Rev. 09/11
3-25
The following symbolic names may be used on deployment together with a
VIPA PLC by selecting "S73&400" server:
Symbol
Memory type
Modificator
Address
DBx
Data block with No. x
B, C, W, S, D, L, F Byte offset
M
Internal memory (flag)
B, C, W, S, D, L, F Byte offset
C
Counter
W, S
Counter No.
T
Timer
W, S
Timer No.
I
Process inputs
B, C, W, S, D, L, F Byte offset
Q
Process outputs
B, C, W, S, D, L, F Byte offset
PI
Peripheral inputs
B, C, W, S, D, L, F Byte offset
PQ
Peripheral outputs
B, C, W, S, D, L, F Byte offset
Modificator Type
Range of values
B
Byte
0 ... 255
C
Byte with sign
-128 ... 127
W
Word
0 ... 65535 (default)
S
Word with sign
-32768 ... 32767
D
DWord
0 ... 4294967296
L
DWord with sign
-2147483648 ... 2147483647
F
Float +/-
3.4E38
With each memory type there is the possibility to access a bit. Here add a #
and the bit no. to the
Address
name.
For the bit no. the values 0 ... 7 may be used.
Note!
If you do not enter a
Modificator
automatically the type "Word" is used. With
data blocks a
Modificator
is always to be entered.
Address
Description
MW4
Flag word 4
CS1
Counter 1, read as word with sign
TS7
Timer 7, read as word with sign
DB2L5
DWord at address 5 (in bytes) in data block 2
IB3
Byte at address 3 (in bytes) in the input area
I5#2 Input
I5.2
Q10#6 Output
Q10.6
Name conventions
for
Address
Symbol
Modificator
Bit access via #
Example
Содержание TM-E 900-1E630
Страница 2: ......
Страница 6: ...Contents Manual VIPA TM E ii HB39E TME RE_900 1E630 Rev 09 11...
Страница 18: ...Chapter 1 Assembly and installation guidelines Manual VIPA TM E 1 10 HB39E TME RE_900 1E630 Rev 09 11...
Страница 26: ...Chapter 2 Hardware description Manual VIPA TM E 2 8 HB39E TME RE_900 1E630 Rev 09 11...
Страница 68: ...Index Manual VIPA TM E A 2 HB39E TME RE_900 1E630 Rev 09 11 M Stich...