Basic error limit (during temperature is 25
°
C, referring to output range)
Measuring
range
Tolerance
Voltage output
1 … 5V
±0.4%
0 … 10V
±0.3%
±10V
±0.2%
Current output
±20mA
±0.2%
0 … 20mA
±0.4%
4 … 20mA
±0.5%
Temperature error
(with reference to the output range)
±0.01%/K
Linearity error
(with reference to the output range)
±0.1%
Repeatability (in steady state at 25°C
referred to the output range)
±0.05%
Output ripple;
range 0 to 50kHz
(referred to output range)
±0.05%
States, Alarms, Diagnosis
Diagnosis alarm
parameterizable
Diagnosis functions
- Sum error monitor
red LED (SF)
- Diagnostic information readable
possible
Substitute value can be applied
yes
Data for choosing an encoder
Voltage input
±10V, 1 ... 5V, 0 ... 10V
120k
Ω
Current input
±20mA, 0 ... 20mA, 4 ... 20mA
110
Ω
Resistors
0...600
Ω
, 0...3k
Ω
10M
Ω
Resistance thermometer
Pt100, Pt1000, Ni100, Ni1000
10M
Ω
Maximum input voltage for voltage
input (destruction limit)
30V
Maximum input current for current
input (destruction limit)
50mA
Connection of the sensor
For measuring voltage
yes
For measuring current
as 2wire transmitter
possible with external power supply
as
4wire
transmitter
yes
For measuring resistance
with
2conductor
connection
yes
Characteristic linearization
for RTD
Pt100, Pt1000, Ni100, Ni1000
Unit for temperature measurement
°
C
continued ...
Содержание 134-4E Series
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 100V ii HB100E EM RE_134 4Ex Rev 08 23...
Страница 18: ...Chapter 1 Basics Manual VIPA System 100V 1 10 HB100E EM RE_134 4Ex Rev 08 23...
Страница 44: ...Chapter 2 Hardware description and deployment Manual VIPA System 100V 2 26 HB100E EM RE_134 4Ex Rev 08 23...
Страница 46: ...Index Manual VIPA System 100V A 2 HB100E EM RE_134 4Ex Rev 08 23 M Stich...