Manual VIPA System 100V
Chapter 2 Hardware description and deployment
HB100E - EM - RE_134-4Ex - Rev. 08/23
2-13
The assignment of a function-no. to a certain channel happens during
parameterization. The function-no. 00h does not influence the function-no.
stored in the permanent parameterization data.
By entering FFh you may deactivate the concerning channel.
The following tables list all functions that are supported by the depending
channel.
You may find the connection type mentioned under "connection" at the
"circuit diagram" above.
Note!
When exceeding the overdrive region, the value 7FFFh (32767) is thrown,
at underrun of the underdrive region the value is 8000h (-32768).
Input range (channel 0 … 2)
No.
Function
Measuring range / representation
Connection
00h
Does not affect permanently stored configuration data.
7Dh
Voltage 0 … 10V
Siemens S7 format
(two’s complement)
-1.76 … 11.76V
/
11.76V= End overdrive region (32511)
0...10V= nominal range (0...27648)
-1.76V= End underdrive region (-4864)
(1)
7Ah
Voltage 1 … 5V
Siemens S7 format
(two’s complement)
0.3 … 5.70V
/
5.70V= End overdrive region (32511)
1...5V= nominal range (0...27648)
0.30V= End underdrive region (-4864)
(1)
28h
Voltage
±
10V
Siemens S7 format
(two’s complement)
±
11.76V
/
11.76V= End overdrive region (32511)
-10...10V= nominal range (-27648...27648)
-11.76V= End underdrive region (-32512)
(1)
7EH
Current 0 … 20mA
Siemens S7 format
(two’s complement)
-3.51 … 23.51mA
/
23.51mA = End overdrive region (32511)
0...20mA = nominal range (0...27648)
-3.51mA = End underdrive region (-4864)
(2)
2Ch
Current
±
20mA
Siemens S7 format
(two’s complement)
±
23.51mA
/
23.51mA = End overdrive region (32511)
-20...20mA = nominal range (-27648...27648)
-23.51mA = End underdrive region (-32512)
(2)
2Dh
Current 4...20mA
Siemens S7 format
(two’s complement)
1.185...+22.81mA
/
22.81mA = End overdrive region (32511)
4...20mA = nominal range (0...27648)
1.18mA = End underdrive region (-4864)
(2)
FFh
Channel not active (turned off)
Function-no.
assignment
Содержание 134-4E Series
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 100V ii HB100E EM RE_134 4Ex Rev 08 23...
Страница 18: ...Chapter 1 Basics Manual VIPA System 100V 1 10 HB100E EM RE_134 4Ex Rev 08 23...
Страница 44: ...Chapter 2 Hardware description and deployment Manual VIPA System 100V 2 26 HB100E EM RE_134 4Ex Rev 08 23...
Страница 46: ...Index Manual VIPA System 100V A 2 HB100E EM RE_134 4Ex Rev 08 23 M Stich...