Chapter 2 Hardware description and deployment
Manual VIPA System 100V
2-14
HB100E - EM - RE_134-4Ex - Rev. 08/23
Input range (channel 3)
No.
Function
Measuring range / representation
Conn.
00h
Does not affect permanently stored configuration data.
01h
Pt100 in 2wire mode
-200 ... +850
°
C
/
in units of 1/10°C, two’s complement
(3, 4)
02h
Pt1000 in 2wire mode
-200 ... +500
°
C
/
in units of 1/10°C, two’s complement
(3, 4)
03h
NI100 in 2wire mode
-50 ... +250
°
C
/
in units of 1/10°C, two’s complement
(3, 4)
04h
NI1000 in 2wire mode
-50 ... +250
°
C
/
in units of 1/10°C, two’s complement
(3, 4)
06h Resistance
measurement
600Ohm 2wire
0 ... 600
Ω
/
705.53
Ω
= End overdrive region (32511)
0 ... 600
Ω
= nominal range (0...27648)
no underdrive region available
(3, 4)
07h Resistance
measurement
3000Ohm 2wire
0 ... 3000
Ω
/
3527.7
Ω
= End overdrive region (32511)
0 ... 3000
Ω
= nominal range (0...27648)
no underdrive region available
(3, 4)
FFh
Channel not active (turned off)
Output range (channel 4, channel 5)
No.
Function
Output range
Conn.
00h
Does not affect permanently stored configuration data
09h
Voltage
±
10V
Siemens S7 format
(two’s complement)
±
11.76V
11.76V= End overdrive region (32511)
-10V...10V = nominal range (-27648...27648)
-11.76 = End underdrive region (-32512)
(3)
0Ah
Voltage 1...5V
Siemens S7 format
(two’s complement)
0...5.704V
5.704V = End overdrive region (32511)
1...5V = nominal range (0...27648)
0V = End underdrive region (-6912)
(3)
0Dh
Voltage 0...10V
Siemens S7 format
(two’s complement)
0...11.76V
11.76V= End overdrive region (32511)
0...10V = nominal range (0...27648)
no underdrive region available
(3)
0Bh
Current
±
20mA
Siemens S7 format
(two’s complement)
±
23.52mA
23.52mA = End overdrive region (32511)
-20...20mA = nominal range (-27648...27648)
-23.52mA = End underdrive region (-32512)
(4)
0Ch
Current 4...20mA
Siemens S7 format
(two’s complement)
0...22.81mA
22.81mA = End overdrive region (32511)
4...20mA = nominal range (0...27648)
0mA = End underdrive region (-6912)
(4)
0Eh
Current 0...20mA
Siemens S7 format
(two’s complement)
0...23.52mA
23.52mA = End overdrive region (32511)
0...20mA = nominal range (0...27648)
no underdrive region available
(4)
FFh
Channel not active (turned off)
Note!
When exceeding the predefined range, 0V res. 0A is shown as value!
Содержание 134-4E Series
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 100V ii HB100E EM RE_134 4Ex Rev 08 23...
Страница 18: ...Chapter 1 Basics Manual VIPA System 100V 1 10 HB100E EM RE_134 4Ex Rev 08 23...
Страница 44: ...Chapter 2 Hardware description and deployment Manual VIPA System 100V 2 26 HB100E EM RE_134 4Ex Rev 08 23...
Страница 46: ...Index Manual VIPA System 100V A 2 HB100E EM RE_134 4Ex Rev 08 23 M Stich...