![VIPA 134-4E Series Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/vipa/134-4e-series/134-4e-series_manual_1029225043.webp)
Manual VIPA System 100V
Chapter 2 Hardware description and deployment
HB100E - EM - RE_134-4Ex - Rev. 08/23
2-25
... continue
Data for choosing an actuator
Output ranges (rated values)
Voltage
1 ... 5V, 0 ... 10V, ±10V
Current
4 ... 20mA, 0 ... 20mA, ±20mA
Load resistance
(in nominal range of the output)
At voltage outputs
min. 1k
Ω
- capacitive load
max. 1
µ
F
At current output
max. 500
Ω
- Inductive load
max. 10mH
Voltage outputs
Short-circuit
protection
yes
Short-circuit current
max. 30mA
Current outputs
No-load voltage
max. 15V
Destruction limit against
voltages/currents applied from outside
Voltage at outputs to M
ANA
max. 16V (30V for 10s)
Current
limited internal up to 30V
Connection of actuators
for voltage output
2conductor connection
for current output
2conductor connection
Parameter data
Input data
8Byte (1 Word per channel)
Output data
4Byte (1 Word per channel)
Parameter data
16Byte
Diagnostic data
12Byte
Dimensions and weight
Dimensions (WxHxD) in mm
101.6x76x48mm
Weight 165g
Содержание 134-4E Series
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 100V ii HB100E EM RE_134 4Ex Rev 08 23...
Страница 18: ...Chapter 1 Basics Manual VIPA System 100V 1 10 HB100E EM RE_134 4Ex Rev 08 23...
Страница 44: ...Chapter 2 Hardware description and deployment Manual VIPA System 100V 2 26 HB100E EM RE_134 4Ex Rev 08 23...
Страница 46: ...Index Manual VIPA System 100V A 2 HB100E EM RE_134 4Ex Rev 08 23 M Stich...