PDT JR. OPERATING INSTRUCTIONS
Operating instructions for the Vinothèque PDT Jr. Thermostat for the QT Series cabinets:
Indicators
There are three colored lights on the left side of the thermostat:
—
PWR (Green)
: The unit is powered.
—
RUN (Yellow)
: The compressor is running. If the light is flashing, the unit is in the five-minute lockout.
—
SET (Red)
: This light flashes when the set point temperature is changed by pressing one of the three
control buttons. It flashes
once
for each press of the Up or Down button and
twice
when the 55 button is
pressed.
When the unit is first turned on, all three lights flash slowly while the thermostat starts up. Once the unit
completes its start-up check, the compressor is locked out for five minutes. During this time, the
RUN
light
will flash slowly.
All three lights will flash rapidly if there is no probe connected to the thermostat.
Buttons
To change the set point temperature, press either the Up or Down button. The SET light will flash once for each
1°F difference. This set point will remain in memory until you change it.
If you forget where the unit is set, pressing the 55 button will reset the set point to 55°F and the set light will
flash twice. The temperature cannot be adjusted below 50°F or above 76°F. Attempting to set the unit outside
of this range will cause the
SET
light to rapidly flash.
Operation
Whenever the compressor shuts off normally, a five-minute lockout period begins and the
RUN
light will flash
slowly.
If the compressor runs for 90 continuous minutes, a five-minute defrost cycle is forced, during which time the
compressor will not run. During this defrost cycle, the
RUN
light will flash rapidly.