- 24 -
8) If the superheat is high, check the subcooling first to see if the refrigerant
charge is sufficient. If the charge is not sufficient, add more refrigerant (Liquid
must always be charged into the hide side when the compressor runs). If the
charge is good, then increase the evaporator suction pressure by turning the
hex nut (5/16”) clockwise.
9) If the superheat is low, then decrease the evaporator suction pressure by
turning the hex nut (5/16”) counter-clockwise.
Fig. 15 Expansion Valve
10) Turn both discharge and suction valves in the back positions.
11) Disconnect the manifold.
9. Pressure, Superheat and Subcooling Readings
CAUTION
To read properly, the service valves must be in the middle
positions.
Complaint
Possible Causes
1) High suction pressure and low head
pressure
Zero superheat and zero subcooling
2) High suction pressure and low head
pressure
Low superheat and low subcooling
3) High suction pressure and high head
pressure
Low superheat and high subcooling
4) High to normal suction pressure and high
head pressure
Low subcooling
5) High suction pressure and high head
pressure
Low superheat and low subcooling
6) High suction pressure and high head
1) Compressor may be bad
2) Expansion valve opened,
too much oil
3) Overcharge
4) Non-condensable gas
5) Air
restricted,
dirty
condenser, bad condenser
fans
6) High cellar temperature,
Содержание WINE-MATE WM-2500SSV
Страница 2: ...1 Important Safety Information...
Страница 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 25 65SFCV Evaporator Unit...
Страница 18: ...17 Fig 5 WM 250 450SCUR Condensing Unit Fig 6 WM 650SCUR Condensing Unit...
Страница 28: ...27 Fig 17 WM 2500 4500SSV LA Electrical Wiring Diagram Fig 18 WM 6500SSV Electrical Wiring Diagram...
Страница 29: ...28 Fig 19 WM 6500SSV LA Electrical Wiring Diagram...