4.4 Sensitive edge
51 52
99
62 63 61
BAR
CO
M
4.5 Stop push button
52 51 62
99
63 64 61
ST
OP
CO
M
5 Changing the programmable parameters
APERTURA
APERTURA
The control panel is programmed by default with the following parameters:
- automatic closing:
30 s
- opening direction:
to the right
- pedestrian opening position: 1 m
Notes:
Do not change the wiring for the electric motors. To reverse the opening direction, follow the procedure described below in paragraph 5.2.
The control panel never needs travel setting as this is automatically measured with each action. When the card is started a full open-close action is per-
formed to calibrate the travel (it takes place at slower speed as the control panel does not know the exact position of the gate).
To change the default settings, follow the instructions provided below.
NOTES: to change the programmable parameters, the gate must be stationary.
WARNING! THE SAFETY DEVICES ARE DISABLED WHILE THE PROGRAMMABLE PARAMETERS ARE BEING CHANGED.
5.1 Changing the automatic closing time
1. While the gate is stationary, press and hold PRG for 2 s; the flashing light comes on and remains steadily lit to indicate that programming is in progress.
The gate closes and reopens.
2. When the gate reaches its opening stop limit, once the desired reclosing time has elapsed (120 s max), press 51 (the gate closes again).
OPENING