7539 Tab Free
The appropriately configured video entryphone can send a notice to the Reception Switchboard art 40510 even if the Due Fili Plus
bus is busy. Unlike other Indoor Stations, only the pair of FP-M terminals can be used as input, not the keys. In this case, the local
door landing call function is lost.
The FP-M operating mode is selected using SaveProg.
1. Render the FP-M input active.
2. The Indoor Station waits to receive the alert from the switchboard.
In the meantime, the chosen signalling is sent to the user according to the table below.
On receipt of the message, the switchboard emits a double beep and displays a red envelope icon to alert the operator.
3. If it does not receive an answer, the Indoor Station resends the message every 10 seconds.
After 5 failed attempts, the Indoor Station stops sending messages.
4. When an Indoor Station receives confirmation of the receipt of the message by the switchboard, the chosen signalling is sent
to the user according to the table below.
Normally the time between the sending of the request and confirmation of reception is less than a second.
5. Until the switchboard calls the Indoor Station to service the request, the Indoor Station resends the message every 120 s. At
each message, the switchboard emits two meets and increases count of messages received.
With each message the switchboard emits two beeps and increases the counter of messages received.
The counter can be viewed by opening the list of alerts in the switchboard.
The sending of messages never terminates.
It continues until the end of the service described in the next point, unless the switchboard is powered off or removed from
the system, in which case the indoor station, after 5 unsuccessful attempts starting from the first timeout of 120 seconds, will
return to standby mode and the Alert signal is no longer sent to the user.
6. If the switchboard operator calls and speaks to the Indoor Station from the list of warnings, and only from this, a message is
sent to the Indoor Station via the Due Fili Plus bus to end the Alert procedure so the related signal is no longer sent to the
user.
1. Enabling
a.
Disabled (default)
b. Enabled
2. Active state polarity
a.
Contact normally open (default)
b.
Contact normally closed
3. Activation delay
a.
0.1 seconds (default)
b.
0.5 seconds
c.
1 second
d.
2 seconds
4. Signalling mode
a. None
b.
LED associated with the Stair Light key (default)
c. Sound
According to the selected signalling type, apart from the first, the timer is as follows:
Alert Configuration
Use SaveProg to select some of the characteristics of the Alert function:
N.B.
: if the Indoor Station is switched off, when it is switched back on again, the function starts again from the beginning.
Alert function configuration via SaveProg
STATUS
LED TIMER
SOUND TIMER
The Indoor Station is waiting to receive a warning
from the switchboard
Flashing with a cycle of 0.5
seconds on / 0.5 seconds off
A 2 KHz tone for 0.2 seconds
The Indoor Station has received confirmation of
receipt of the message from the switchboard
Flashing with a cycle of 0.1
seconds on / 0.1 seconds off
A 1 KHz tone for 0.1 seconds
Advanced configurations