RS10
3 . 3 . 1 C onnecting control b uttons and k ey sw itch
Normally open contacts (the red AP/CH or APED LEDS light up when the selector or buttons connected in parallel are operated):
3 . 4 C onnecting control b uttons and k ey sw itch
,
normally open contacts (the APCH or aped LEDs come on when the selector or the buttons connected in parallel are operated) the APCH input controls
opening or closing the gate completely, the APED input controls partial gate opening or closing:
Fig. 6
T erminal
numb er D escription
Input ty pe
14 -17 -2 0
COM: Control inputs common (permanent GND)
-
13
FCAP: Opening limit switch Input if the gate opens to the right (P18 = R), closing limit switch input if the gate opens to
the left (P18 = L)
Normally closed
15
FCCH: Closing limit switch Input if the gate opens to the right (P18 = R), opening limit switch input if the gate opens to
the left (P18 = L)
Normally closed
16
OPEN: Opening-only button input, dedicated for timer or detector for magnetic induction coils
Normally open
18
APCH: Sequential control input, to govern the complete travel of the gate
Normally open
19
APED: Sequential control input, to govern the pedestrian travel of the gate
Normally open
2 1
STOP: Input for stopping the gate
Normally closed
2 2
PHOTO: Photocell input, active during gate closing
Normally closed
2 3
STPA: Input for edges or internal photocell, active during gate closing and opening
Normally closed
3 . 5 C onnection of timer or detector w ith magnetic induction
with normally open contact (the open LED comes on when the timer or magnetic induction detector are operated) the OPEN input commands full opening
of the gate, until the contact is closed, the gate opens and remains in the open position, the APCH, APED commands and saved remote controls are not
active until the contact is reset from closed to open, after the automatic closing time set with the PAUSE trimmer, the gate closes, this input is used to
open and hold open the gate at the times of greatest influx:
Fig. 7
Fig. 8
3 . 3 Input w iring
The control panel is supplied with non-jumpered normally closed safety inputs (STOP, FOTO, STPA), add a jumper between the common (COM) and
input you do not intend to use.
EN
12
6
3
9
11
10
8
7
5
4
2
1
TIMER
17 18 19 20 21 22 23
COM
FCAP
FCCH
APRI
COM
APCH
APED
COM
ST
OP
FOT
O
STP
A
COM
APCH
APED
Pulsante comando APCH
Pulsante comando APED
COM
N.O.
N.C.
N.C.
N.O.
COM
COM
APRI