ENGLISH - 21
5.3 - Control with reduction switch.
It is possible to force the thermostat onto the reduced temperature
with a switch .
If the thermostat is on the
Comfort temperature
, closing the con-
tact connecting the terminal to line
L
with the switch will activate
the reduced temperature .
For the
switchover
to take place, the contact
must
stay closed
for at least 10 s .
On turning off the switch, the thermostat will return to the previously
set function .
Warnings.
The switches must have clean contacts (luminous switches must not
be used) and the maximum distance must not exceed 100 metres.
L
N
Switch