By adjusting the temperature differential, the system can be pre-
vented from continually switching on or off; systems with high thermal
inertia (for example, with cast iron radiators) require a low temperature
differential value, and systems with low thermal inertia (for example,
fan coil units) require a higher value.
Example:
If the ambient temperature is set to 20 °C and the tem-
perature differential is set to 0.3 °C, the system will come on when
the ambient temperature falls to 19.9 °C and will go off when it
reaches 20.3 °C.
Press the
selection button on
THERM DIF
and, using the rotary
knob, set the desired value (can be selected between 0.1 °C and
1°C); lastly press the
selection button to confirm.
9.7.5 DATE/TIME
This option is used to set the current day and time on the timer-
thermostat.
Press the
selection button on
DATE/TIME
; using the rotary
knob, set the day, month, year, hours and minutes, pressing the
selection button to confirm each of the choices made (see
figure 30).
N.B.
Changes for summer time must be made by the user.
9.7.6 12h/24h
This option is used to set the mode, twenty-four hour or
AM
and
PM
, with which to show the time on the display of the timer-
thermostat.
Press the
selection button on
12h/24h
and, using the rotary
knob, set the desired mode (
12 h
or
24 h
); lastly press the
selection button to confirm.
Figure 30
Содержание 01911
Страница 1: ...01911 Surface electronic chronothermostat Instruction handbook CLIMAPIÙ ...
Страница 2: ...Space for noting the three digit PIN number used as the lockout password ...
Страница 4: ......
Страница 8: ...4 Figure 2 Figure 3 ...
Страница 9: ...5 Figure 4 Figure 5 ...
Страница 11: ...7 83 5 mm 60 mm Figure 6 ...