27/44 NT00000792-KUBAIR-F400-ECOWATT-VENTDRIVE-AN-220314
5.4 Relay operation
Max 1 A at 30 VDC and 24 VAC.
The Output 1 relay is a run relay. The relay switches when the run signal is given.
Output 2 is a fault relay. The relay switches when the motor stops after 5 restart attempts.
CONTROLLER TERMINALS
R2 No
R2 C
R2 Nc
R1 No
R1 C
R1 Nc
25
24
23
22
21
20
Output 1 relay
Running relay
Output 2 relay
Fault relay
Max 1A at
30VDC and 24VAC
30VDC / 24VAC
Power on request
indicator
Fault or power off
indicator
GND
GND
Communication parameters
Register
Address
Function
Scale
Resolution
Fault value
4x0033
32
Relay configuration 1
0 - 6
0 - Desactivated
1 – N/A
2 – Running Start
3 – AlarmOut
4 – Running Spin
5 – N/A
6 – Single Error Alarm
2 – Running Start
4x0034
33
Relay configuration 2
0 - 6
0 - Desactivated
1 – N/A
2 – Running Start
3 – AlarmOut
4 – Running Spin
5 – N/A
6 – Single Error Alarm
3 – AlarmOut