5.3.3 Input Registers
Available Input Registers are shown in tables below.
Input Registers: 34 (R)
0x04: Read
Register
Address
Function
Range
EC-config (PM)
FC-config (AC)
Resolution
Unit
Resolution
Unit
3x0001
0
Drive Type
1000 - 65535
1
-
1
-
3x0002
1
AOC SW version
0 - 65535
0.01
-
0.01
-
3x0003
2
MOC SW version
0 - 65535
0.01
-
0.01
-
3x0004
3
PrcOut
0 - 10000
0.01
%
0.01
%
3x0005
4
RPMOut
0 - 3000
1
RPM
0.01
Hz
3x0006
5
Intern Temp
-5000 - 15000
0.01
ºC
0.01
ºC
3x0007
6
V In (RMS)
0 - 500
1
V
1
V
3x0008
7
I Out
0 - 65535
1
mA
1
mA
3x0009
8
Power In (filtered)
0 - 20000
1
W
1
W
3x0010
9
I Ripple
0 - 65535
1
mA
1
mA
3x0011
10
Operation Minutes
0 - 1439
1
Min.
1
Min.
3x0012
11
Operation Day
0 - 9999
1
Day
1
Day
3x0013
12
V Ripple
0 - 500
1
V
1
V
3x0014
13
Config file variant
AA - ZZ
2 ASCII characters
2 ASCII characters
3x0015
14
Config file version
100 - 32000
0.01
-
0.01
-
3x0016
15
ExternSet
0 - 10000
1
mV
1
mV
3x0017
16
Power Supply
0 - 600
1
V
1
V
3x0018
17
OverVoltageCount
0 - 65535
1
-
1
-
3x0019
18
AOC SW variant
-
-
-
-
-
3x0020
19
AOC Boot SW
0 - 65535
0.01
-
0.01
-
3x0021
20
MOC Boot SW
0 - 65535
0.01
-
0.01
-
3x0022
21
Motor Cfg. Var.
0 - 65535
1
-
1
-
3x0023
22
Motor Cfg. Ver.
0 - 65535
0.01
-
0.01
-
3x0024
23
Fan Cfg. Var.
0 - 65535
1
-
1
-
3x0025
24
Fan Cfg. Ver.
0 - 65535
0.01
-
0.01
-
3x0026
25
User Data Var.
0 - 65535
1
-
1
-
3x0027
26
User Data Ver.
0 - 65535
0.01
-
0.01
-
3x0028
27
IOM SW version
0 - 65535
0.01
-
0.01
-
3x0029
28
V DC Bus (Peak)
0 - 800
1
V
1
V
3x0030
29
V Motor (Peak)
0 - 500
1
V
1
V
3x0031
30
Power In (unfilterd)
0 - 15000
1
W
1
W
3x0032
31
Power Consumpt.
0 - 999
1
Wh
1
Wh
3x0033
32
Power Consumpt.
0 - 999
1
kWh
1
kWh
3x0034
33
Power Consumpt.
0 - 65535
1
MWh
1
MWh
Input Registers: 18 (R)
0x04: Read
Register
2Address
Function
Range
Active state
Unit
3x8193
8192
Production week
0100-5399
1
WWYY
3x8194
8193
Production order number LO
0-9999
1
-
3x8195
8194
Production order number HI
0-9999
10000
-
3x8196
8195
Serial number of batch
0-65535
1
-
3x8197
8196
Product name Char0
0-65535
-
2 x ACSII Char
3x8198
8197
Char1 + Char2
0-65535
-
2 x ACSII Char
3x8199
8198
Char3 + Char4
0-65535
-
2 x ACSII Char
3x8200
8199
Char5 + Char6
0-65535
-
2 x ACSII Char
3x8201
8200
Char7 + Char8
0-65535
-
2 x ACSII Char