26/44 NT00000792-KUBAIR-F400-ECOWATT-VENTDRIVE-AN-220314
Register Address
Function
Common for EC (PM) & FC (AC) configuration
Range / Value
Resolution / Option
Unit
4x0034
33
IO_Opt2 config (IOM)
0
Disabled
-
1
N/A
-
2
RunningStart
Output
3
AlarmOut
Output
4
RunningSpin
Output
5
Set output status via coil
stat 24
Output
6
Single Error Alarm
Output
100
Disabled
-
101
Start/Stop
Input
102
AlarmReset
Input
103
Disabled
Input
104
Invert 0-10V (open =
inverted)
Input
105
Rotation
Input
106
Firemode
Input
107
N/A
-
108
Invert 0-10V
(open = not inverted)
Input
109
Motor output off
Input
110
N/A
-
111
FiremodeMax
Input
112
Digital Dual Speed
Input
4x0035
34
AnalogOut1 config (IOM)
0
Disabled
-
1
ActSpeed
-
2
TBD
-
4x0036
35
Thermistor config (IOM)
0
Disabled
-
1
Motor Overheat PTC
-
2
TBD
-
4x0037
36
AnalogIn2 config (IOM)
0
Disabled
-
1
TBD
-
2
TBD
-
4x0038
37
Thermistor threshold
1 - 65000
1
Ω
4x0039
38
Max Windmilling Time
0 - 65000
1
Sec
4x0049
48
Jumping Frequency_Low 1
or Dual Speed 1
MinRPM – MaxRPM 1
RPM
4x0050
49
Jumping Frequency_High 1
or Dual Speed 2
MinRPM – MaxRPM 1
RPM
4x0051
50
Jumping Frequency_Low 2 MinRPM – MaxRPM 1
RPM
4x0052
51
Jumping Frequency_High 2 MinRPM – MaxRPM 1
RPM
4x0053
52
Jumping Frequency_Low 3
or Firemode Max speed
MinRPM – MaxRPM 1
RPM
4x0054
53
Jumping Frequency_High 3 MinRPM – MaxRPM 1
RPM
"TBD" = To be done – for future use