For information, calculation of the air flow rate according to the set point :
Q
v
= K x
√
2,5 x set point, with K the fan coefficient
Size of KUBAIR
®
F400 ECOWATT
®
Coeff. K
500
250
630
428
710
473
5.10 KUBAIR
®
F400 ECOWATT
®
3-phases - COP constant pressure control
During operation at constant pressure, the controller regulates the speed of the roof fan to obtain the set
pressure. If the display is present on the roof fan, it will show you the pressure in Pa. The pressure set
point can be adjusted by the potentiometer in the controller, by a CVF ON/OFF + variation remote con-
trol, by an external 0-10V output or by Modbus BMS.
5.10.1 Wiring
COP type factory assembly and wiring, with or without display.
Connection of the power supply to the
INTZ switch to be done by the customer.
INTZ 15 A
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19
M
Green/Yellow
U
V
W
+24V
Fir
e
+24V
Start/Stop
Green
Shun
t
Shun
t
Thermo switch
N/F
Speed-Output
GN
D
+24V
GN
D
An2
+10V
GN
D
An1
NC
COM
NO
Relay fault
PE
L1
L2
Controller
Black
Green/Yellow
Brown
A B
PE
U
V
W
Black
Blue
Red
P
L2
L1
INTZ 15A
400V power supply
2
4
3 1 5
1 2 3 4
SW1
1
2
3
Off
Off
On
TDPD Display
Only on TED with display types
L3
Grey
Grey
6
L3
Brown
SPRD
pressure
sensor
Only on TED COP types
without display
Yellow
Black
Red
Only on KUBAIR® COP
without display
TDPD Display
only on KUBAIR®
with display types