NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
• by a VRPZ voltage variator (allowing 0 / LS / HS operation with adjustable LS and HS),
•
flow rate control by Modbus BMS.
VAV - Regulation according to the deviation between the set point / external measurement
During operation at variable speed, the controller regulates the speed of the roof fan according to the set
point-measurement deviation. The set point is adjusted with the potentiometer built into the controller or
a CVF type external control. If the display is present on the roof fan, it will show you the flow rate in m
3
/h.
Example of slaving and VAV regulation according to measurement of the outside temperature:
VAV slaved according to the temperature sensor
VAV with regulation according to the deviation between
the set point / external measurement
M
Ventilateur Extraction
TED F400 ECOWATT®
T°
Extract roof fan
M
Ventilateur Extraction
TED F400 ECOWATT®
O/I
CVF
Commande Locale
T°
Extract roof fan
Local control
5.8.1 Wiring
VAV type factory assembly and wiring, with or without display.
Connection of the power supply to the
INTZ switch to be done by the customer.
INTZ 15 A
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19
M
Green/Yellow
U
V
W
+24V
Fir
e
+24V
Start/Stop
Green
Shun
t
Thermo switch
N/F
Speed-Output
GN
D
+24V
GN
D
An2
+10V
GN
D
An1
NC
COM
NO
Relay fault
PE
L1
L2
Controller
Black
Green/Yeloow
Brown
A B
PE
U
V W
Black
Blue
Red
P
L2
L1
INTZ 15A
400V
Power supply
ROOF FAN
2
4
3 1 5
1 234
SW1
1
2
3
Off
On
On
TDPD Display
Only on TED with
display types
L3
Grey
6
L3
Brown
CASING
TDPD Display
only on KUBAIR®
with display types