Convertisseur USB - RS485
Terminaison 120Ω 1 nF
RX / TX +
RX / TX -
5 6 7 8
Invento 01
5 6 7 8
Invento 02
5 6 7 8
Invento 03
Segment
Dérivation
A1 B1 A2 B2
A1 B1 A2 B2
A1 B1 A2 B2
It is imperative to address a unique address to each controller.
ModBus address :
COMPACTO : Register 7 of Holding Registers.
INVENTO : Register 9 of Holding Registers.
Refer to the corresponding paragraph below for the connection and the setting of your casing.
5.2.5
Default configuration settings
A USB converter with RS 485 is necessary for you to connect to the registers via a PC, as well as an
interface of the same type as ModBus Doctor.
Single-phase model*
3-phase model*
MODBUS address
1
80
Baut rate
19200
START Bit
1
STOP Bit
1
Parity
NONE
* For additional information refer to the roof fan controller manual (available on www.vim.fr).
5.2.6 Input register table
The "Input Register" table allows you to read the following information:
Register
Fonction
Resolution
Description
Single-phase model
4
Speed
1
rpm
8
Power
0,1
W
9
An1 input
0,01
V
10
An2 input
0,01
V
11
Pot input
0,01
V
3-phase model
0
Speed
1
rpm
2
Power
1
W
9
An1 input
0,01
V
10
An2 input
0,01
V
For all other information on the setting of Modbus, contact the After-Sales service department.