34/44
NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
0-LS-HS installation diagram, with adjustable LS and HS
The PV and the GV are adjusted by a VRPZ VOLTAGE variator (accessory not supplied). 0-LS-HS choice
with the VRPZ.
%
S
OUT
2
+24
1
E
E
E
SP MAX M/A
Gnd
Gnd
Gnd
Gnd
Gnd
Gnd
L
L
L
N
N
N
EVGAS
INPUT
relay
230V
Sortie
Light
Speed
230V
Moteur
0-10V
MES
OUT
24V
3 4
+24V
Start/Stop
10
GND
Controller
VRPZ
9
AN1
230V Power supply
Wiring for regulation according to the deviation between the set point / external measurement
ON/
OFF
1
2
3
4
5
P
Power supply (V)
Output signal GN
D
+24V
Start/Stop
CVF
Instead of
the potentiometer
Instead of
the shunt
CVF
Controller
*0-10V output examples: temperature sensor, humidity sensor.
No 24V power supply if BMS connection.
For a BMS, controlling is only done by the 0-10V signal and GND.
9 10 11
+10V
GN
D
An1
3 4
0 - 10V
Output
Controller
12VDC Maxi
Output signal
GN
D
Sensor power supply
*24Vdc -
40mA Maxi
0 - 10V OUTPUT
12 13 14
An2
GN
D
+24V
*
15 16
Speed-Output
GN
D
Shunt
5.8.2 Speed adjustment
By potentiometer, CVF type remote control or 0-10V signal.
By default the roof fan is set to its maximum speed, in bold in the table below.
The potentiometer in the controller allows you to change the speed of the turbine to adjust the flow rate.
The adjustment can be given by the CVF type remote control or a 0-10V signal.
Correspondence table between the potentiometer graduation, the voltage applied on terminal 10 and the speed.
Graduation
potentiometer
Voltage (V)
at terminal 10
KUBAIR
®
F400 ECOWATT
®
500
KUBAIR
®
F400 ECOWATT
®
630
KUBAIR
®
F400 ECOWATT
®
710
0
0
200 rpm
200 rpm
200 rpm
2
2
460 rpm
400 rpm
410 rpm
4
4
720 rpm
600 rpm
620 rpm
6
6
980 rpm
790 rpm
830 rpm
8
8
1 240 rpm
980 rpm
1 040 rpm
10
10
1 500 rpm
1 180 rpm
1 250 rpm