ENGLISH
A u t o m a t i c o r m a n u a l c a l i b r a t i o n
The automatic calibration of the PID control was chosen by default, so
that the control of the preheating coil responds as precisely as possi
-
ble to the requirement.
Procedure for manual calibration:
- Return to the parameter menu with the code 1234,
- Select the PID parameter,
- Assign the MAN value.
- Wait for the the parameter to be applied.
- On the main screen, press briefly on
and select the
value ON via the arrows to launch the calibration procedure.
For more details on the procedure call the SAV (after sales service)
9 .
A D V A NC ED C O NF IGU R A T IO N
9 . 1 Ho u r l y p r o g r a m m i n g
The controller has several clocks for the individual programming of: Reduced flow, Normal flow, Stop.
Holiday periods can be programmed and the change to summer time is automatic.
A night cooling function can be programmed to start the AHU outside the scheduled periods.
Configuring the clock:
Only the operating ranges are programmed (the fan is off outside these ranges).
The installer can thus define two operating ranges at normal speed (default speed or high speed) and at
''reduced'’ speed (low speed when two speeds are possible). Normal speed is prioritised over reduced
speed, and, in the case of overlapping programming times, the unit will operate at normal speed.
For each speed, two ranges can be entered per day.
For example:
High Speed can be defined from
08h00 to 12h00 in Period 1
and from
14h00 to 18h00 in Period 2
and Low Speed from
06h00 to 08h00 in Period 1
and from
12h00 to 21h00 in Period 2
The automaton will then control the fan in the following manner:
Normal speed
timer program
ON
ON
OFF
OFF
OFF
DAY (H)
LS
HS
Reduce speed
timer program
Complet fan
speed program
Advanced
settings
Welcome screen
Sub menu
Centrale simple flux
2012-11-12
Systeme Fonct. Normal
C : 24.0C /R: 17.8C
Running mode
Temperature
Air control
Time settings
Access rights