NT00000535-KSDR-ECOWATT-48-88-120-160-200-AN-190905
40/88
ENGLISH
8 . 1
Simplified Menus / Access
The KSDR ECOWATT
®
AHU provides quick access to the main functions.
Access: There are 3 levels of access to the controller:
•
U s e r l e v e l
(no password) - Access to the start/stop functions - Auto or LS/HS and increase of the
temperature setpoint (± 3 °C)
•
O p e r a t o r l e v e l
(password) - read and write access to the settings and parameters, but no access to
the system configuration
•
M a s t e r l e v e l
(password) - read and write access to the settings and parameters, as well as access
to the system configuration
The KSDR ECOWATT
®
can operate according to 3 operating methods:
•
C A V
: Constant airflow operation
•
V A V
: Variable speed operation
•
C O P
: Constant pressure operation
The KSDR ECOWATT
®
can manage an ASR ECOWATT extraction unit type TED F400, KUBAIR F400 or
controlled JBRB interlocked with the ASR system.
Access to adjustement
program
Access to adjustement
menu
O K
.
8
7
9
4
5
3
2
1
Enter PIN code:
1111
Cancel
Enter PIN code: 1111
and select OK
Setting
Ventilation mode
Select the control mode
Main screen:
Pass word:
Control mode adjustement:
6
0
Menu screen:
Menu
CAV
COP
VAV
21.4°C
2012-06-26 14:02
2500 m3 /h
Run mode : ON
Temperature setpoint
Maintenance needed
U s e r l e v e l :
adjustment of the temperature set point and selection of the unit operating mode (use of the
time programme, stopping the unit, or possible overriding at a given speed). These two temperature and
ventilation functions are accessible in two specific menus dedicated to this use.
Temperature
Ventilation mode
+21.0°C
Desired (setp.)
Supply air T°
+21.9°C
+10.8°C
Room T°
Constant supply air temperature
+20.9°C
Extract T°
Fan control off, munual,
auto ...
Selec temperature
setpoint
Menu VAV
Manual 0.0V
1371m3/h
10 %
OR
OR
Menu CAV
Off
Off
Off
Low speed
Higt speed
Auto
Auto
Auto
Menu COP
300m3/h
966Pa
10%
Actual flow
Actual pressure
Actual output
+21°C
Main screen:
Menu screen:
Access to adjustement
menu
Value can be modified but
pressing the value on the
screen. PIN code (1111) is
asking to modify T° setpoint
Menu
21.4°C
2012-06-26 14:02
2500 m3 /h