VK1001 STANDARD
RESPONSE UPRIGHT
SPRINKLER (K5.6)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 2 of 4
Form No. F_102420 Rev 22.1 February 22, 2022
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
Sprinkler
Base Part
Number
Size
1: Finishes
2: Temperature Ratings
NPT
Inch
BSPT
mm
Description
Suffix
1
Nominal Rating
Bulb Color Max. Ambient Ceiling
Temperature
2
Suffix
23867
1/2
--
Brass
A
135 °F (57 °C)
Orange
100 °F (38 °C)
A
23879
--
15
Chrome
F
155 °F (68 °C)
Red
100 °F (38 °C)
B
White Polyester
3,5
M-/W
175 °F (79 °C)
Yellow
150 °F (65 °C)
D
Black Polyester
3,5
M-/B
200 °F (93 °C)
Green
150 °F (65 °C)
E
ENT
3,4,5
JN
286 °F (141 °C)
Blue
225 °F (107 °C)
G
OPEN
--
--
Z
Example
: 23867MB/W = VK1001 with white polyester finish and 155 °F (68 °C) nominal temperature rating. This sprinkler is to be
installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above
the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
Accessories
Sprinkler Wrenches (see Figure 1):
Standard (straight) Wrench: Part number 23559MB.
Sprinkler Cabinet:
A. Up to 6 sprinklers: Part number 01724A
B. 6-12 sprinklers: Part number 01725A
Footnotes
1.
Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3.
UL Listed as corrosion resistant.
4.
FM Approved as corrosion resistant.
5.
The corrosion resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart.
These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or
suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
5. OPERATION
During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinklers are available through a network of domestic and international distributors. See the website for the closest
distributor or contact Viking.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.