The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

SPRINKLER OVERVIEW

Page 2 of 3

Form No. F_080814       18.12.06       Rev 14.1.P65

VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a 

water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow 

arrow in the direction of discharge. Marked “SIDEWALL” on the deflector with an arrow and the word “FLOW”. (Note: Some 

vertical sidewall sprinklers can only be installed in the upright or pendent position—in this case, the sprinkler will also be marked 

“UPRIGHT” or “PENDENT”.)

HORIZONTAL SIDEWALL (HSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The special deflector 

provides a water spray pattern outward in a quarter-spherical pattern. Most of the water is directed away from the nearby wall 

with a small portion directed at the wall behind the sprinkler. The top of the deflector is oriented parallel with the ceiling or roof. 

The flow arrows point in the direction of discharge. Marked “SIDEWALL” and “TOP” with an arrow and the word “FLOW”.

EXTENDED COVERAGE (EC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum 

dimensions indicated in the individual listings. Maximum area of coverage, minimum flow rate, orifice size, and nominal K-Factor 

are specified in the individual listings. EC sprinklers are intended for Light-Hazard occupancies with smooth, flat, horizontal ceil-

ings unless otherwise specified. In addition to the above markings, the sprinkler is marked “EC”.

QUICK RESPONSE (QR) SPRINKLER: A spray sprinkler with a fast- actuating operating element. The use of quick response 

sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction (AHJ) prior to installing.

QUICK RESPONSE EXTENDED COVERAGE (QREC) SPRINKLER: A spray sprinkler designed to discharge water over an area 

having the maximum dimensions indicated in the individual listing. This is a sprinkler with an operating element that meets the 

criteria for quick response. QREC sprinklers are only intended for Light Hazard occupancies. The sprinkler is marked “QREC”.

FLUSH SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The unit is mounted 

flush with the ceiling or wall, with the fusible link exposed. Upon actuation, the deflector extends beyond the ceiling or wall to 

distribute water discharge. The sprinkler is marked “SSP”, “PEND”, or “SIDEWALL” and “TOP”.

CONCEALED SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The sprinkler is 

hidden from view by a cover plate installed flush with the ceiling or wall. During fire conditions, the cover plate detaches, and 

upon sprinkler actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked 

“SSP”, “PEND”, or “SIDEWALL” and “TOP”.  

RECESSED SPRINKLER: A spray sprinkler assembly intended for installation with a concealed piping system. The assembly con-

sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond 

the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity. Refer to the appropriate technical data page 

for allowable sprinkler models, temperature ratings, and occupancy classifications. DO NOT RECESS ANY SPRINKLER NOT 

LISTED FOR USE WITH THE ESCUTCHEON.

CORROSION-RESISTANT SPRINKLER: A special service sprinkler with non-corrosive protective coatings, or that is fabricated 

from non-corrosive material, for use in atmospheres that would normally corrode sprinklers.

DRY SPRINKLER: A special-service sprinkler intended for installation on dry pipe systems or wet pipe systems where the sprinkler 

is subject to freezing temperatures. The unit consists of a sprinkler permanently secured to an extension nipple with a sealed 

inlet end to prevent water from entering the nipple until the sprinkler operates. The unit MUST be installed in a tee fitting. Dry 

upright sprinklers are marked with the “B” dimension [distance from the face of the fitting (tee) to the top of the deflector]. Dry 

pendent and sidewall sprinklers are marked with the “A” dimension [the distance from the face of fitting (tee) to the finished 

surface of the ceiling or wall].

LARGE DROP SPRINKLER: A type of special application sprinkler used to provide fire control of specific high-challenge fire haz-

ards. Large drop sprinklers are designed to produce an umbrella-shaped spray pattern downward with a higher percentage of 

“large” water droplets than standard spray sprinklers. The sprinkler has an extra-large orifice with a nominal K-Factor of 11.2. 

Marked “HIGH CHALLENGE” and “UPRIGHT”.

EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER: A sprinkler intended to provide fire suppression of specific high-

challenge fire hazards through the use of a fast response fusible link, 14.0, 16.8, or 25.2 nominal K-Factor, and special deflector. 

ESFR sprinklers are designed to produce high-momentum water droplets in a hemispherical pattern below the deflector. This 

permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the 

development of a high-challenge fire. Marked “ESFR” and “UPRIGHT” or “PEND”.

INTERMEDIATE LEVEL/RACK STORAGE SPRINKLER: A standard spray sprinkler assembly designed to protect its operating 

element from the spray of sprinklers installed at higher elevations. The assembly consists of a standard or large orifice upright 

or pendent sprinkler with an integral upright or pendent water shield and guard assembly. Use only those sprinklers that have 

been tested and listed for use with the assembly. Refer to the technical data page for allowable sprinkler models.

RESIDENTIAL SPRINKLER: A sprinkler intended for use in the following occupancies: one- and two-family dwellings with the fire 

protection sprinkler system installed in accordance with NFPA 13D; residential occupancies up to four stories in height with the 

fire protection system installed in accordance with NFPA 13R; and where allowed by the Authority Having Jurisdiction in resi-

dential portions of any occupancy with the fire protection system installed in accordance with NFPA 13.

Содержание VK1001

Страница 1: ...6m VdS Approved Certificate no G 422003 Refer to the Approval Chart and Design Criteria for requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressure 7 PSI 0 5 bar Rated to cULus 250 PSI 17 2 bar WWP FM CE LPCB and VdS 175 PSI 12 bar WWP Factory tested hydrostatically to 500 PSI 34 5 bar Thread size 1 2 NPT 15 mm BSPT Nominal K factor 5 6 U S 80 6 metric Glass b...

Страница 2: ...inklers Part number 01725A Footnotes 1 Where a dash is shown in the Finish suffix designation insert the desired Temperature Rating suffix See example above 2 Based on NFPA 13 NFPA 13R and NFPA 13D Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 UL Listed as corrosion resistan...

Страница 3: ...I 12 bar CE6 LPCB7 VdS8 23867 1 2 B1 A1 A1 23879 15 B1 A1 A1 Approved Temperature Ratings A 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C B 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C Approved Finishes 1 Brass Chrome White Polyester 3 4 Black Polyester 3 4 and ENT 4 5 Footnotes 1 Base Part number is shown For complete part number refer to Viking s current price schedule 2 This t...

Страница 4: ...rs shall be followed DESIGN CRITERIA FM FM Approval Requirements The Viking VK1001 Standard Response Upright Sprinkler is FM Approved as standard response Non Storage upright sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheet 2 0 FM Global Loss Prevention Data She...

Страница 5: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 6: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 7: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 8: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 9: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 10: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 11: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 12: ...he sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may affe...

Страница 13: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Страница 14: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Страница 15: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Страница 16: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Страница 17: ...ssories painting plating coating or modification may render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERAL INFORMATION A potential product performance issue may exist when listed products are combined with unlisted product s that have not been evaluated...

Отзывы: