LED References
In addition to the LCD Display, the control board LEDs monitor the various circuits of the
control board. Use the table below to identify the corresponding “TS Ref#” and refer to
pages 36-39 for further troubleshooting.
TROUBLESHOOTING
# LED
Status
Meaning
Page 39
TS Ref#(s)
1
“Magnetic
Lock Relay”
OFF
At Closed Limit and Magnetic Lock Relay state is closed across “COM” &
“N.C.”. Gate should be at the Close Limit.
SOLID
Not at Closed Limit and Magnetic Lock Relay state is closed across “COM” &
“N.O.”. Gate should not be at the Close Limit
2
“Check Motor” OFF
Normal Condition.
SOLID
The control board is sending power to the motor but the circuit is open.
7, 8
3
“Battery Low” OFF
Normal Condition.
SOLID
Does not apply to Solar Units.
FLASHING
Batteries critically low. Check power supply to the operator. (pg 21).
4
“POWER”
OFF
No power to control board (pg 21) or board is in sleep mode.
5
SOLID
Normal Condition.
5
“Radio”
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the
Radio terminal or when more than one device is connected (pg 29, 40).
9, 10
6
“UL”
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the UL
terminal (pg 10-11, 28, 40).
9, 10, 16,
22
7
“Re-Open”
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the Re-
Open terminal or when more than one device is connected (pg 10-11, 28,
31, 40).
9, 10, 16,
22
8
“ATG”
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the ATG
terminal (pg 30, 40).
9, 10