TECHNICAL DATA

January 12, 2007

Deluge Devices 270h

RELEASE CONTROL PANEL

MODEL B-1

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

ITEM NO.

PART 

NUMBER

DESCRIPTION

QTY.

NOTES

1

07912

Zone Relay Module 4XZM (Included with Panel)

1

1

Optional

1

2

07909

Transmitter Module 4XTM

1

Optional

3

--

LED Interface Module 4XLM

1

Optional

4

07911

Remote Annunciator Module RZA-4X

1

Optional

5

07917

Voltage, Current Meters 4XMM

1

Optional

6

07920

Battery, 12V, 7 Amp Hr. Capacity

2

 OR

2

Two Batteries Required

2

07921

Battery, 12V, 12 Amp Hr. Capacity

2

 OR

2

09867

Battery, 12V, 18 Amp Hr. Capacity

2

2

09866

Battery Box, Required when using 18 AH Batteries

7

07915

Fuses, 4 Amp

4

Included

8a

07914

Resistor, Dummy Load (Notifi er 71245)

6

Included

8b

08391

Resistor, Dummy Load (Notifi er 27072)

2

Included

9

07919

Power Relay

1

Optional

10a

--

Battery Plug Wire Ass’y (7 Amp Battery)

1

Included

10b

08285

Battery Plug Wire Ass’y (12 Amp Battery)

1

Included

11

07913

Resistor, End-of-Line (Notifi er 71252)

1

Optional

12a

08389

Mother Board 110 Volt

3

1

Included

3

12b

08390

Mother Board 220 Volt

3

1

Included

3

-- Indicates replacement part not available

1

This unit can support a second Zone Relay Module 4XZM in addition to the one included with the panel.

2

Always use two batteries of the same amperage. Order batteries separately after performing power calculations

 to determine size of battery required to meet standby requirements.

3

Voltage of AC Power Supply determines voltage of Mother Board required.

Figure 2 - 

Replacement Parts

Revised page replaces page 270 a-g dated August 17, 2006

(Added California State Fire Marshal approval)

Form No. F_063092

OBSOLETE

Содержание B-1

Страница 1: ...he appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depress ing the Tone or Alarm Silence button the LED will remain steadily illuminated until the panel is reset 2 LISTINGS AND APPROVALS Refer to Table 1 3 TECHNICAL DATA I Specifications A Enclosure Dimensions 16 125 high x 14 625 wide x 5 375 deep 50 cm x 37 1 cm x 13 7 cm Weight 23 lbs 10 4 ...

Страница 2: ...25 AMPS Supervised Circuitry Power limited circuitry except for Municipal Box output Fuses 2AG 4 amperes Maximum allowable voltage drop due to wiring 2 VDC End of Line resistor 4 7K provided Note leave E O L resistors provided on all unused circuits Note Wiring must be configured to maintain a minimum voltage of 20 4V on release circuits Contact the Viking distributor for a list of compatible indi...

Страница 3: ...Last Event Recall Follow procedure printed in Par 3 Owner s Manual provided with panel R Zone Disable Function Follow procedure printed in Par 3 Owner s Manual provided with panel S Battery Fail and Earth Fault supervision See Figure 2 for location of LEDs T Discharge timer option Latched 10 or 15 minutes Refer to Par 3 Owner s manual included with panel Also refer to installation standards Techni...

Страница 4: ...ompatible devices Also refer to appropriate Fire Protection Equipment Approval Guides Wire all alarm initiating devices sequentially for proper supervision Pull required conductors through the knockouts provided Prior to connecting to the panel verify continuity of all circuitry Prior to connecting to the panel check for and correct any short circuits Make electrical connections to control panel f...

Страница 5: ...ting and inspection requirements that must be followed WARNING ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS I Tests A Prior to proceeding wit...

Страница 6: ... place the system back in service II Maintenance CAUTION DISCONNECT ALL POWER SOURCES BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM AGED BY REMOVING AND OR INSERTING CARDS MODULES OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER GIZED 7 AVAILABILITY The Viking Model B 1 Release Control Panel is available through a network of domestic and international distributors See the Viking ...

Страница 7: ...its must acti vate to energize the release circuit ON OFF OFF OFF OFF 3 Dual Hazard Combined Release Two release circuits Two detection circuits Activation of EITHER detection circuit energizes BOTH release cir cuits OFF ON OFF OFF OFF 4 Dual Hazard Split Release Two release circuits Two detection circuits Activation of detection circuit No 1 energizes release circuit No 1 Activation of detection ...

Страница 8: ...p 4 Included 8a 07914 Resistor Dummy Load Notifier 71245 6 Included 8b 08391 Resistor Dummy Load Notifier 27072 2 Included 9 07919 Power Relay 1 Optional 10a Battery Plug Wire Ass y 7 Amp Battery 1 Included 10b 08285 Battery Plug Wire Ass y 12 Amp Battery 1 Included 11 07913 Resistor End of Line Notifier 71252 1 Optional 12a 08389 Mother Board 110 Volt3 1 Included3 12b 08390 Mother Board 220 Volt3...

Отзывы: