TECHNICAL DATA

January 12, 2007

Deluge Devices 270c

RELEASE CONTROL PANEL

MODEL B-1

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

N. Front Panel Control Switches 

(Refer to Figure 1)

Switch 1: Tone Silence
Switch 2: Alarm Silence - Tone Silence and Alarm Silence control switches can be activated to acknowledge alarms. A second 
“trouble” will resound the piezo.
Switch 3: Alarm Activate -The Alarm Activate switch may be used to activate indicating circuits and relays.
Switch 4: System Reset - The Reset switch clears any activated output circuits. If alarm or trouble conditions exist when the reset 
switch is pushed, they will re-activate the panel.

O. Front Panel Zone Status LEDs

When the panel is activated, zone status LEDs illuminate, to indicate the status of Zone 1, Zone 2, Alarm Pressure, and Auxiliary 
Supervisory circuits. 
Alarm (red) LEDs indicate activation of a detection device. 
Trouble (yellow) LEDs indicate electrical circuit failure, such as short circuits and loose wires.

P. Front Panel System Status LEDs

The presence of AC Power is indicated by a constant green LED, indicating normal conditions.
Alarm (red), Trouble (yellow), and Supervisory (yellow) LEDs activate as required to indicate System Alarm, Release operation, 
Supervisory Device activation, and Circuit trouble. 
LEDs also illuminate to indicate when the Alarm Silence switch has been activated.

Q. Last Event Recall

Follow procedure printed in Par-3 Owner’s Manual provided with panel.

R. Zone Disable Function 

Follow procedure printed in Par-3 Owner’s Manual provided with panel.

S. Battery Fail and Earth Fault supervision

See Figure 2 for location of LEDs 

T. Discharge timer option

Latched, 10 or 15 minutes. Refer to Par-3 Owner’s manual included with panel. Also refer to installation standards, Technical 
Data, and all Authorities Having Jurisdiction when using timer confi gurations.
Output circuits protected against false activation by two step command sequence

U. Slide in zone identification labels

Spare labels included in Par-3 Owner’s Manual provided with panel.

V. Other Features

Piezo Sounder
Alarm signals are latching
Trouble signals are self restoring
Alarm and Trouble resound

II. Ordering Information

Part Numbers - Refer to Table 1
Available since 1991

A. Modules and Accessories 

(order separately)

1. Batteries

Two batteries of the same AH rating are required. 
12V 7 Amp-Hour Viking P/N 07920
12V 12 Amp-Hour Viking P/N 07921 12V 18 Amp-Hour Viking P/N 09867
Plug-in connector is provided with the Panel.
See POWER CALCULATIONS to determine which batteries meet standby battery requirements.

2. Zone Relay Module (4XZM) 

(Viking Part No. 07912)

Model B-1 Panels can accommodate a second 4XZM Zone Relay Module (one included in each panel) or one of the following 
two Modules:

3. Transmitter Module (4XTM) 

(Viking P/N 07909) 

Provides a supervised output for local energy municipal box transmitter and alarm and trouble  reverse polarity circuits.

4. LED Interface Module (4XLM) 

(Viking P/N 07910) 

For Remote Annunciator (RZA-4X) described below (Required for NYC approval). 












OBSOLETE

Содержание B-1

Страница 1: ...he appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depress ing the Tone or Alarm Silence button the LED will remain steadily illuminated until the panel is reset 2 LISTINGS AND APPROVALS Refer to Table 1 3 TECHNICAL DATA I Specifications A Enclosure Dimensions 16 125 high x 14 625 wide x 5 375 deep 50 cm x 37 1 cm x 13 7 cm Weight 23 lbs 10 4 ...

Страница 2: ...25 AMPS Supervised Circuitry Power limited circuitry except for Municipal Box output Fuses 2AG 4 amperes Maximum allowable voltage drop due to wiring 2 VDC End of Line resistor 4 7K provided Note leave E O L resistors provided on all unused circuits Note Wiring must be configured to maintain a minimum voltage of 20 4V on release circuits Contact the Viking distributor for a list of compatible indi...

Страница 3: ...Last Event Recall Follow procedure printed in Par 3 Owner s Manual provided with panel R Zone Disable Function Follow procedure printed in Par 3 Owner s Manual provided with panel S Battery Fail and Earth Fault supervision See Figure 2 for location of LEDs T Discharge timer option Latched 10 or 15 minutes Refer to Par 3 Owner s manual included with panel Also refer to installation standards Techni...

Страница 4: ...ompatible devices Also refer to appropriate Fire Protection Equipment Approval Guides Wire all alarm initiating devices sequentially for proper supervision Pull required conductors through the knockouts provided Prior to connecting to the panel verify continuity of all circuitry Prior to connecting to the panel check for and correct any short circuits Make electrical connections to control panel f...

Страница 5: ...ting and inspection requirements that must be followed WARNING ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS I Tests A Prior to proceeding wit...

Страница 6: ... place the system back in service II Maintenance CAUTION DISCONNECT ALL POWER SOURCES BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM AGED BY REMOVING AND OR INSERTING CARDS MODULES OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER GIZED 7 AVAILABILITY The Viking Model B 1 Release Control Panel is available through a network of domestic and international distributors See the Viking ...

Страница 7: ...its must acti vate to energize the release circuit ON OFF OFF OFF OFF 3 Dual Hazard Combined Release Two release circuits Two detection circuits Activation of EITHER detection circuit energizes BOTH release cir cuits OFF ON OFF OFF OFF 4 Dual Hazard Split Release Two release circuits Two detection circuits Activation of detection circuit No 1 energizes release circuit No 1 Activation of detection ...

Страница 8: ...p 4 Included 8a 07914 Resistor Dummy Load Notifier 71245 6 Included 8b 08391 Resistor Dummy Load Notifier 27072 2 Included 9 07919 Power Relay 1 Optional 10a Battery Plug Wire Ass y 7 Amp Battery 1 Included 10b 08285 Battery Plug Wire Ass y 12 Amp Battery 1 Included 11 07913 Resistor End of Line Notifier 71252 1 Optional 12a 08389 Mother Board 110 Volt3 1 Included3 12b 08390 Mother Board 220 Volt3...

Отзывы: