TECHNICAL DATA

January 12, 2007

Deluge Devices 270f

RELEASE CONTROL PANEL

MODEL B-1

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

CAUTION! SIMULTANEOUS OPERATION OF BOTH DETECTION CIRCUITS ON ANY SYSTEM UTILIZING CROSS-ZONE DETECTION 
WILL RESULT IN OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE MAIN WATER SUPPLY CONTROL VALVE WILL 
CAUSE WATER TO FLOW INTO THE SPRINKLER PIPING.

Operate individual detectors, following instructions listed in technical data for the detector used. See Figure 2 for output circuits 
and relays that should activate for the system used. “Detection” circuits are latching (except when configured for optional “timed 
shut-off”. See Owner’s Manual).
When Test is complete, push “System Reset”. Conditions should return to normal.
Refer to technical data for the system used to open main water supply control valve and place the system back in service.

II. Maintenance

CAUTION: DISCONNECT ALL POWER SOURCES BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM-
AGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER-
GIZED.

7. AVAILABILITY

The Viking Model B-1 Release Control Panel is available through a network of domestic and international distributors.  See the Viking 
Corp. Web site  for closest distributor or contact The Viking Corporation.

8. GUARANTEES

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

2.

3.
4.

Table 1 - Part Numbers and Approvals

Name

Power Supply

Approvals

Viking Part 

No.

Par-3

110 VAC 50/60Hz

UL

1

, FM, NYC

3

 and CSFM

4

07907

Par-3C

110 VAC 50/60Hz

cUL

2

07953

Par-3E

220 VAC 50/60Hz

FM

07908

1

 UL listed Releasing Device Control Unit (UOJZ)

2

 cUL and CSA approved Par-3C

Accepted by New York City Department of Buildings (MEA 89-92-E) when confi gured for Single Hazard-Two 

Zone operation (See Figure 1) and equipped with LED Interface Module (4XLM) and Remote Annuncitor 
(RZA-4X) See ACCESSORIES

4

 Listed by the California State Fire Marshall (7770-0533:105)

OBSOLETE

Содержание B-1

Страница 1: ...he appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depress ing the Tone or Alarm Silence button the LED will remain steadily illuminated until the panel is reset 2 LISTINGS AND APPROVALS Refer to Table 1 3 TECHNICAL DATA I Specifications A Enclosure Dimensions 16 125 high x 14 625 wide x 5 375 deep 50 cm x 37 1 cm x 13 7 cm Weight 23 lbs 10 4 ...

Страница 2: ...25 AMPS Supervised Circuitry Power limited circuitry except for Municipal Box output Fuses 2AG 4 amperes Maximum allowable voltage drop due to wiring 2 VDC End of Line resistor 4 7K provided Note leave E O L resistors provided on all unused circuits Note Wiring must be configured to maintain a minimum voltage of 20 4V on release circuits Contact the Viking distributor for a list of compatible indi...

Страница 3: ...Last Event Recall Follow procedure printed in Par 3 Owner s Manual provided with panel R Zone Disable Function Follow procedure printed in Par 3 Owner s Manual provided with panel S Battery Fail and Earth Fault supervision See Figure 2 for location of LEDs T Discharge timer option Latched 10 or 15 minutes Refer to Par 3 Owner s manual included with panel Also refer to installation standards Techni...

Страница 4: ...ompatible devices Also refer to appropriate Fire Protection Equipment Approval Guides Wire all alarm initiating devices sequentially for proper supervision Pull required conductors through the knockouts provided Prior to connecting to the panel verify continuity of all circuitry Prior to connecting to the panel check for and correct any short circuits Make electrical connections to control panel f...

Страница 5: ...ting and inspection requirements that must be followed WARNING ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS I Tests A Prior to proceeding wit...

Страница 6: ... place the system back in service II Maintenance CAUTION DISCONNECT ALL POWER SOURCES BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM AGED BY REMOVING AND OR INSERTING CARDS MODULES OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER GIZED 7 AVAILABILITY The Viking Model B 1 Release Control Panel is available through a network of domestic and international distributors See the Viking ...

Страница 7: ...its must acti vate to energize the release circuit ON OFF OFF OFF OFF 3 Dual Hazard Combined Release Two release circuits Two detection circuits Activation of EITHER detection circuit energizes BOTH release cir cuits OFF ON OFF OFF OFF 4 Dual Hazard Split Release Two release circuits Two detection circuits Activation of detection circuit No 1 energizes release circuit No 1 Activation of detection ...

Страница 8: ...p 4 Included 8a 07914 Resistor Dummy Load Notifier 71245 6 Included 8b 08391 Resistor Dummy Load Notifier 27072 2 Included 9 07919 Power Relay 1 Optional 10a Battery Plug Wire Ass y 7 Amp Battery 1 Included 10b 08285 Battery Plug Wire Ass y 12 Amp Battery 1 Included 11 07913 Resistor End of Line Notifier 71252 1 Optional 12a 08389 Mother Board 110 Volt3 1 Included3 12b 08390 Mother Board 220 Volt3...

Отзывы: