Viking B-1 Скачать руководство пользователя страница 5

TECHNICAL DATA

January 12, 2007

Deluge Devices 270e

RELEASE CONTROL PANEL

MODEL B-1

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

Connect the long RED lead to the positive terminal of one battery, and the long black lead to the negative terminal of the 
other.
Place batteries inside the battery compartment of the Par-3 Release Control Panel with the unused terminals toward the open 
door. Install batteries in the upright position only.
Plug the plug-in connector to J9 on the main board of the panel. (Refer to Figure 2 and VIKING FIELD WIRING DIAGRAMS.) 
DO NOT install jumper at this time.

To energize the panel and place the system in service: 

Energize the AC power supply to the panel. The Piezo will sound, and the “System Trouble” and “Power Trouble” LEDs will 
flash.  
Use the jumper (short) wire to connect the unused negative terminal of one battery with the unused positive terminal of the other 
battery. The Piezo should silence, and the “System Trouble” and “Power Trouble”  LEDs should stop flashing.
Perform appropriate tests to verify proper operation of the system.
After placing the system in service, close and lock the panel to prevent tampering with the unit.

When installing optional cards, modules, inter-connecting cables, or other associated equipment, refer to MAINTENANCE, technical 
data for the optional equipment, and Owner’s Manual provided with the panel.

6. INSPECTIONS, TESTS AND MAINTENANCE

NOTICE: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM AND DEVICES IN PROPER OPERAT-
ING CONDITION. THE VIKING MODEL B-1 PAR-3 RELEASE CONTROL PANEL MUST BE KEPT FREE OF FOREIGN MATTER AND 
ENVIRONMENTAL CONDITIONS THAT COULD IMPAIR ITS OPERATION.

For minimum maintenance and inspection requirements, refer to NFPA 25. In addition, the Authority Having Jurisdiction may have ad-
ditional maintenance, testing, and inspection requirements that must be followed.   

WARNING: ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE 
MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES 
HAVING JURISDICTION. CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS.

I. Tests 
A. Prior to proceeding with tests:

Verify that installation complies with instructions in the Owner’s Manual provided with the panel and the appropriate VIKING 
FIELD WIRING DIAGRAMS for the system used.
Notify the Authority Having Jurisdiction and all those in the area affected by the test.

B. Alarm Activate Switch 

To test alarm bell, waterfl ow bell circuits and alarm, detection, and waterfl ow relays:

Push “Alarm Activate” (See Figure 1). Note: “Alarm Activate” is a latching function. “Alarm Silence” will silence indicating circuits 
and System Alarm Relay and light the Alarm Silenced LED.
When test is complete, push “System Reset”. Conditions should return to normal.

C. Waterflow

To test waterfl ow alarm on Viking pre-action and Viking deluge systems, consult technical literature for the system used:

Turn the Alarm Test Valve to “Test” position. See Table 2 for output circuits and relays that should activate for the system used. 
“Waterflow” circuits are latching.
When test is complete return the Alarm Test Valve to the normal position and push “System Reset”. Conditions should return to 
normal.

C. Detection 

To test detection circuits:

Close main water supply control valve, placing the system out of service.

CAUTION! FOR DELUGE AND SINGLE OR NON-INTERLOCKED PREACTION SYSTEMS, PERFORMING THIS TEST RESULTS IN 
OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE MAIN WATER SUPPLY CONTROL VALVE WILL CAUSE WATER TO 
FLOW INTO THE SPRINKLER PIPING.

CAUTION! FOR DOUBLE-INTERLOCKED SYSTEMS, SIMULTANEOUS OPERATION OF A DETECTOR AND LOWERING OF SUPER-
VISORY PRESSURE IN THE SPRINKLER PIPING WILL RESULT IN OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE 
MAIN WATER SUPPLY CONTROL VALVE WILL CAUSE WATER TO FLOW INTO THE SPRINKLER PIPING.

b.

c.

d.

11.

12.

13.
14.

1.

2.

1.

2.

1.

2.

1.

OBSOLETE

Содержание B-1

Страница 1: ...he appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depress ing the Tone or Alarm Silence button the LED will remain steadily illuminated until the panel is reset 2 LISTINGS AND APPROVALS Refer to Table 1 3 TECHNICAL DATA I Specifications A Enclosure Dimensions 16 125 high x 14 625 wide x 5 375 deep 50 cm x 37 1 cm x 13 7 cm Weight 23 lbs 10 4 ...

Страница 2: ...25 AMPS Supervised Circuitry Power limited circuitry except for Municipal Box output Fuses 2AG 4 amperes Maximum allowable voltage drop due to wiring 2 VDC End of Line resistor 4 7K provided Note leave E O L resistors provided on all unused circuits Note Wiring must be configured to maintain a minimum voltage of 20 4V on release circuits Contact the Viking distributor for a list of compatible indi...

Страница 3: ...Last Event Recall Follow procedure printed in Par 3 Owner s Manual provided with panel R Zone Disable Function Follow procedure printed in Par 3 Owner s Manual provided with panel S Battery Fail and Earth Fault supervision See Figure 2 for location of LEDs T Discharge timer option Latched 10 or 15 minutes Refer to Par 3 Owner s manual included with panel Also refer to installation standards Techni...

Страница 4: ...ompatible devices Also refer to appropriate Fire Protection Equipment Approval Guides Wire all alarm initiating devices sequentially for proper supervision Pull required conductors through the knockouts provided Prior to connecting to the panel verify continuity of all circuitry Prior to connecting to the panel check for and correct any short circuits Make electrical connections to control panel f...

Страница 5: ...ting and inspection requirements that must be followed WARNING ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS I Tests A Prior to proceeding wit...

Страница 6: ... place the system back in service II Maintenance CAUTION DISCONNECT ALL POWER SOURCES BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM AGED BY REMOVING AND OR INSERTING CARDS MODULES OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER GIZED 7 AVAILABILITY The Viking Model B 1 Release Control Panel is available through a network of domestic and international distributors See the Viking ...

Страница 7: ...its must acti vate to energize the release circuit ON OFF OFF OFF OFF 3 Dual Hazard Combined Release Two release circuits Two detection circuits Activation of EITHER detection circuit energizes BOTH release cir cuits OFF ON OFF OFF OFF 4 Dual Hazard Split Release Two release circuits Two detection circuits Activation of detection circuit No 1 energizes release circuit No 1 Activation of detection ...

Страница 8: ...p 4 Included 8a 07914 Resistor Dummy Load Notifier 71245 6 Included 8b 08391 Resistor Dummy Load Notifier 27072 2 Included 9 07919 Power Relay 1 Optional 10a Battery Plug Wire Ass y 7 Amp Battery 1 Included 10b 08285 Battery Plug Wire Ass y 12 Amp Battery 1 Included 11 07913 Resistor End of Line Notifier 71252 1 Optional 12a 08389 Mother Board 110 Volt3 1 Included3 12b 08390 Mother Board 220 Volt3...

Отзывы: