TECHNICAL DATA

January 12, 2007

Deluge Devices 270b

RELEASE CONTROL PANEL

MODEL B-1

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

Note: leave E-O-L resistors provided, on all unused circuits.
Detector loop current is suffi cient to ensure operation of one alarmed 
detector per zone.
Supervisory current: 5mA (including End-of-Line Resistor)

G. Heat Detectors:

 Detection circuits allow for installation of any number of listed or ap-
proved normally open thermal detectors.

H. Smoke Detectors:

Contact the Viking distributor for a list of compatible smoke detectors, 
information concerning the maximum number of smoke detectors 
allowed per zone, and standby power requirements for the smoke 
detector used. Also, refer to appropriate Fire Protection Equipment 
Approval Guides.  
For supervised four-wire smoke detectors, connect the Power Su-
pervision Relay to the last detector base 24V screw terminals.
See ACCESSORIES.

I. Indicating Appliance and Releasing (output) Circuits

Two Style Y and two Style Y/Z circuits
Output 1: Alarm Bell(Style Y/Z)
Output 2: Waterfl ow or Trouble Horn (Style Y/Z)
Output 3: Releasing Circuit 1 (Style Y)
Output 4: Releasing Circuit 2 or Trouble Horn(Style Y)
Normal operating voltage: 24VDC
Total current available to all four ci RMS regulated power 
output circuit, not to exceed: 2.25 AMPS 
Maximum signaling current per circuit: 2.25 AMPS
Supervised Circuitry Power limited circuitry (except for Municipal 
Box output)
Fuses: 2AG, 4 amperes 
Maximum allowable voltage drop due to wiring: 2 VDC.
End-of-Line resistor: 4.7K  (provided)
Note: leave E-O-L resistors provided, on all unused circuits.
Note: Wiring must be confi gured to maintain a minimum voltage of 20.4V on release circuits. 
Contact the Viking distributor for a list of compatible indicating appliances and releasing devices. Also, refer to Viking Technical 
Data and appropriate Fire Protection Equipment Approval Guides.  

J. Alarm Relay

Basic panel includes one non-silenceable Form-C dry alarm contact rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resis-
tive). 

K. Trouble Relay

Basic panel includes one Form-C dry alarm contact rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive). Trouble relay 
will silence when trouble condition is cleared.

L. Zone Relay Module  

Model B-1 Panels include one Zone Relay Module (4XZM) providing dry Form-C contacts  controlled by each of the four output 
circuits plus one general alarm and one panel/fi eld-wiring trouble relay. See Table 2.

M. Power Outputs

Four-wire Smoke Detector Power (resettable): Up to 200 mA total (four-wire smoke detector power plus non-resettable power 
combined) DC current available. Maximum ripple voltage: 10mV p/p.
Non-resettable Power: Up to 200 mA total (four-wire smoke detector power plus non-resettable power combined) DC current 
available. 
Maximum ripple voltage: 10mV p/p.
RMS Regulated Power: Total current available for external devices: 0.5 amp (subtracted from 2.25 A available to indicating ap-
pliance circuits) DC current available. 
Maximum ripple voltage: 100mV p/p.















Figure 1

OBSOLETE

Содержание B-1

Страница 1: ...he appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depress ing the Tone or Alarm Silence button the LED will remain steadily illuminated until the panel is reset 2 LISTINGS AND APPROVALS Refer to Table 1 3 TECHNICAL DATA I Specifications A Enclosure Dimensions 16 125 high x 14 625 wide x 5 375 deep 50 cm x 37 1 cm x 13 7 cm Weight 23 lbs 10 4 ...

Страница 2: ...25 AMPS Supervised Circuitry Power limited circuitry except for Municipal Box output Fuses 2AG 4 amperes Maximum allowable voltage drop due to wiring 2 VDC End of Line resistor 4 7K provided Note leave E O L resistors provided on all unused circuits Note Wiring must be configured to maintain a minimum voltage of 20 4V on release circuits Contact the Viking distributor for a list of compatible indi...

Страница 3: ...Last Event Recall Follow procedure printed in Par 3 Owner s Manual provided with panel R Zone Disable Function Follow procedure printed in Par 3 Owner s Manual provided with panel S Battery Fail and Earth Fault supervision See Figure 2 for location of LEDs T Discharge timer option Latched 10 or 15 minutes Refer to Par 3 Owner s manual included with panel Also refer to installation standards Techni...

Страница 4: ...ompatible devices Also refer to appropriate Fire Protection Equipment Approval Guides Wire all alarm initiating devices sequentially for proper supervision Pull required conductors through the knockouts provided Prior to connecting to the panel verify continuity of all circuitry Prior to connecting to the panel check for and correct any short circuits Make electrical connections to control panel f...

Страница 5: ...ting and inspection requirements that must be followed WARNING ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS I Tests A Prior to proceeding wit...

Страница 6: ... place the system back in service II Maintenance CAUTION DISCONNECT ALL POWER SOURCES BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM AGED BY REMOVING AND OR INSERTING CARDS MODULES OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER GIZED 7 AVAILABILITY The Viking Model B 1 Release Control Panel is available through a network of domestic and international distributors See the Viking ...

Страница 7: ...its must acti vate to energize the release circuit ON OFF OFF OFF OFF 3 Dual Hazard Combined Release Two release circuits Two detection circuits Activation of EITHER detection circuit energizes BOTH release cir cuits OFF ON OFF OFF OFF 4 Dual Hazard Split Release Two release circuits Two detection circuits Activation of detection circuit No 1 energizes release circuit No 1 Activation of detection ...

Страница 8: ...p 4 Included 8a 07914 Resistor Dummy Load Notifier 71245 6 Included 8b 08391 Resistor Dummy Load Notifier 27072 2 Included 9 07919 Power Relay 1 Optional 10a Battery Plug Wire Ass y 7 Amp Battery 1 Included 10b 08285 Battery Plug Wire Ass y 12 Amp Battery 1 Included 11 07913 Resistor End of Line Notifier 71252 1 Optional 12a 08389 Mother Board 110 Volt3 1 Included3 12b 08390 Mother Board 220 Volt3...

Отзывы: