TECHNICAL DATA
January 12, 2007
Deluge Devices 270a
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]
1. DESCRIPTION
The Viking Model B-1 Par-3 Release Control Panel is a supervised, 24 Volt, microprocessor-
controlled Release Control Panel. The panel is designed to operate up to two electric release
devices (usually solenoid valves) in the release piping of deluge or preaction systems. The
panel is available for use with either 120 VAC or 230 VAC power supplies. A built-in battery com-
partment holds two 12 Volt batteries that are charged by an internal battery charger. Batteries
are available to provide up to 90 hours of backup power during AC power failure.
The Model B-1 Release Control Panel can be used with a wide range of compatible initiating
devices, such as heat (including linear heat detection systems like the Protectowire Systems),
photoelectric, ionization, and smoke detectors.
A dip switch ‘Function Selector’ allows fi eld programming for one of four possible input/output
combinations (refer to Table 2).
In fi re conditions, when an initiating device circuit (or predetermined combination of circuits) is
energized, the panel activates a combination of release device circuits and alarm circuits ac-
cording to the ‘Function Selector’ setting. On the panel’s display board, the appropriate Alarm,
Trouble, and Supervisory LED’s will fl ash until the event has been acknowledged. After depress-
ing the Tone or Alarm Silence button, the LED will remain steadily illuminated until the panel is
reset.
2. LISTINGS AND APPROVALS
Refer to Table 1
3. TECHNICAL DATA
I. Specifications
A. Enclosure
Dimensions: 16.125” high x 14.625” wide x 5.375” deep (50 cm x 37,1 cm x 13,7 cm)
Weight: 23 lbs. (10,4 kg)
Finish: Red Enamel
Vented Enclosure
B. Environment
Temperature: 32 °F to 120 °F (0 °C to 48 °C)
Humidity: 85% Relative Humidity (non-condensing) at 90 °F (32 °C) maximum
C. AC Power
Par-3 and Par-3C: 120 VAC, 50/60 Hz, 1.2 amps
Par-3E: 230 VAC, 50 Hz, 0.65 amps
Wire size: minimum #14 AWG with 600 V insulation
D. Battery
Type- Lead Acid
Maximum charging circuit: 27.6V, 1.5 A See ACCESSORIES for batteries available from Viking.
E. Initiating Device (Input) Circuits
Four style B (Class B)/Style D (Class A) circuits
Input 1: Detection Circuit
Input 2: Detection Circuit
Input 3: Waterfl ow (Alarm Pressure Switch)
Input 4: Supervisory Circuit
F. System Alarm
Power limited circuitry
Fuses: 2AG, 4 amperes
Normal operating voltage: 24VDC (ripple = 10mV peak to peak)
Alarm Current: 15mA minimum
Short circuit current: 40mA maximum
Maximum detector current in standby: 2 milliamps (peak) per zone
Maximum loop resistance: 100 ohms
End-of-Line resistor: 4.7K (provided)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Revised page replaces page 270 a-g dated August 17, 2006
(Added California State Fire Marshal approval)
Form No. F_063092