TECHNICAL DATA

January 12, 2007

Deluge Devices 270a

RELEASE CONTROL PANEL

MODEL B-1

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

1. DESCRIPTION

The Viking Model B-1 Par-3 Release Control Panel is a supervised, 24 Volt, microprocessor-
controlled Release Control Panel. The panel is designed to operate up to two electric release 
devices (usually solenoid valves) in the release piping of deluge or preaction systems. The 
panel is available for use with either 120 VAC or 230 VAC power supplies. A built-in battery com-
partment holds two 12 Volt batteries that are charged by an internal battery charger. Batteries 
are available to provide up to 90 hours of backup power during AC power failure. 
The Model B-1 Release Control Panel can be used with a wide range of compatible initiating 
devices, such as heat (including linear heat detection systems like the Protectowire Systems), 
photoelectric, ionization, and smoke detectors. 
A dip switch ‘Function Selector’  allows fi eld programming for one of four possible input/output 
combinations (refer to Table 2). 
In fi re conditions, when an initiating device circuit (or predetermined combination of circuits) is 
energized, the panel activates a combination of release device circuits and alarm circuits ac-
cording to the ‘Function Selector’ setting. On the panel’s display board, the appropriate Alarm, 
Trouble, and Supervisory LED’s will fl ash until the event has been acknowledged. After depress-
ing the Tone or Alarm Silence button, the LED will remain steadily illuminated until the panel is 
reset.

2. LISTINGS AND APPROVALS

Refer to Table 1 

3. TECHNICAL DATA

I. Specifications

A. Enclosure

Dimensions: 16.125” high x 14.625” wide x 5.375” deep (50 cm x 37,1 cm x 13,7 cm)
Weight: 23 lbs. (10,4 kg)
Finish: Red Enamel
Vented Enclosure

B. Environment

Temperature: 32 °F to 120 °F (0 °C to 48 °C)
Humidity: 85% Relative Humidity (non-condensing) at 90 °F (32 °C) maximum

C. AC Power

Par-3 and Par-3C: 120 VAC, 50/60 Hz, 1.2 amps
Par-3E: 230 VAC, 50 Hz, 0.65 amps
Wire size: minimum #14 AWG with 600 V insulation

D. Battery 

Type- Lead Acid
Maximum charging circuit: 27.6V, 1.5 A See ACCESSORIES for batteries available from Viking.

E. Initiating Device (Input) Circuits

Four style B (Class B)/Style D (Class A) circuits
Input 1: Detection Circuit
Input 2: Detection Circuit
Input 3: Waterfl ow (Alarm Pressure Switch)
Input 4: Supervisory Circuit  

F. System Alarm

Power limited circuitry
Fuses: 2AG, 4 amperes 
Normal operating voltage: 24VDC (ripple = 10mV peak to peak)
Alarm Current: 15mA minimum
Short circuit current: 40mA maximum
Maximum detector current in standby: 2 milliamps (peak) per zone
Maximum loop resistance: 100 ohms
End-of-Line resistor: 4.7K (provided)



















Viking Technical Data may be found on 

The Viking Corporation’s Web site at 

http://www.vikinggroupinc.com.

The Web site may include a more recent 

edition of this Technical Data Page.

Revised page replaces page 270 a-g dated August 17, 2006

(Added California State Fire Marshal approval)

Form No. F_063092

OBSOLETE

Содержание B-1

Страница 1: ...he appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depress ing the Tone or Alarm Silence button the LED will remain steadily illuminated until the panel is reset 2 LISTINGS AND APPROVALS Refer to Table 1 3 TECHNICAL DATA I Specifications A Enclosure Dimensions 16 125 high x 14 625 wide x 5 375 deep 50 cm x 37 1 cm x 13 7 cm Weight 23 lbs 10 4 ...

Страница 2: ...25 AMPS Supervised Circuitry Power limited circuitry except for Municipal Box output Fuses 2AG 4 amperes Maximum allowable voltage drop due to wiring 2 VDC End of Line resistor 4 7K provided Note leave E O L resistors provided on all unused circuits Note Wiring must be configured to maintain a minimum voltage of 20 4V on release circuits Contact the Viking distributor for a list of compatible indi...

Страница 3: ...Last Event Recall Follow procedure printed in Par 3 Owner s Manual provided with panel R Zone Disable Function Follow procedure printed in Par 3 Owner s Manual provided with panel S Battery Fail and Earth Fault supervision See Figure 2 for location of LEDs T Discharge timer option Latched 10 or 15 minutes Refer to Par 3 Owner s manual included with panel Also refer to installation standards Techni...

Страница 4: ...ompatible devices Also refer to appropriate Fire Protection Equipment Approval Guides Wire all alarm initiating devices sequentially for proper supervision Pull required conductors through the knockouts provided Prior to connecting to the panel verify continuity of all circuitry Prior to connecting to the panel check for and correct any short circuits Make electrical connections to control panel f...

Страница 5: ...ting and inspection requirements that must be followed WARNING ANY SYSTEM MAINTENANCE THAT REQUIRES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS I Tests A Prior to proceeding wit...

Страница 6: ... place the system back in service II Maintenance CAUTION DISCONNECT ALL POWER SOURCES BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM AGED BY REMOVING AND OR INSERTING CARDS MODULES OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER GIZED 7 AVAILABILITY The Viking Model B 1 Release Control Panel is available through a network of domestic and international distributors See the Viking ...

Страница 7: ...its must acti vate to energize the release circuit ON OFF OFF OFF OFF 3 Dual Hazard Combined Release Two release circuits Two detection circuits Activation of EITHER detection circuit energizes BOTH release cir cuits OFF ON OFF OFF OFF 4 Dual Hazard Split Release Two release circuits Two detection circuits Activation of detection circuit No 1 energizes release circuit No 1 Activation of detection ...

Страница 8: ...p 4 Included 8a 07914 Resistor Dummy Load Notifier 71245 6 Included 8b 08391 Resistor Dummy Load Notifier 27072 2 Included 9 07919 Power Relay 1 Optional 10a Battery Plug Wire Ass y 7 Amp Battery 1 Included 10b 08285 Battery Plug Wire Ass y 12 Amp Battery 1 Included 11 07913 Resistor End of Line Notifier 71252 1 Optional 12a 08389 Mother Board 110 Volt3 1 Included3 12b 08390 Mother Board 220 Volt3...

Отзывы: