LT0186 Issue 2.80
27 July 2012
Page 1 of 10
T-GEN 50
24V Alert & Evacuate Tone Generator
INSTALLATION AND OPERATING INSTRUCTIONS
The VIGILANT T-GEN 50 is a self-contained AS 2220 and ISO 8201 Alert and Evacuate tone generator, with speaker
line supervision and speech. It has been designed to connect directly to fire alarm panels, but may be connected to other
suitable digitised equipment.
T-GEN 50 is available in 2 versions (see page 8 for a full list of available items and accessories):
PA0766
Tones, fault supervision and speech. Contains (SF0341)
–
Speech IC with 4 pre-recorded messages
that are inserted into the Alert and Evacuate tones. A microphone input is also provided for
emergency public address and for recording messages different to the standard messages supplied.
A suitable microphone is Part Number ME0290.
PA0886
Same as PA0766 except fitted with SF0309 software and SF0342 speech IC in which the alert
message is a recorded bell sound. Alert and evacuate tones may separately be disabled so only the
recorded messages are played. DIP switches 5-8 select different functions.
Feature
PA0766
PA0886
24 VDC, fault supervision, optional PA microphone
YES
YES
Alert Tone (can be separately disabled on PA0886)
YES
YES/Disable
Pre-recorded Alert speech message
YES
BELL TONE
Evacuation Tone AS 2220 or ISO 8201 selectable
YES
YES/Disable
Pre-recorded Evacuation messages selectable
YES
YES
Microphone input for emergency public address
YES
YES
Custom message recording facility
YES
YES
Software and speech IC fitted
SF0308, SF0341
SF0309, SF0342
Switches and links used to select different options
YES
YES
Recommended for use in Schools and hospitals
NO
YES
These instructions apply to units with V1.70 software onwards. Refer to LT0186 Issue 2.30 for instructions for earlier
software versions.
A pre-assembled Building Occupant Warning System (BOWS) that utilises the T-GEN 50 is available in 50W and 100W
versions (ordering codes FP1021 and FP1022).
CHECKING THE KIT
Before commencing installation, please ensure that the following items are present and undamaged:
1 x T-GEN 50 Board
1 x Installation & Operating Instructions (LT0186)
1 x Background music loom For connecting an external music source to the T-GEN MUSIC input
1 x 6.3mm spacer
Mounting T-GEN on earth stud
1 x M4 washer
Mounting T-GEN on earth stud
1 x M4 nut
Mounting T-GEN on earth stud
6 x PCB standoffs
Mounting T-GEN
1 x 2k7 resistor
Optional Isolate Indication
1 x 3k3 resistor
ELD for MX4428 & F3200 Ancil Relays
2 x 10k resistor
-ALM Input ELD resistor, MX4428 Ancil Relay ELD
1 x 56k resistor
100V line ELD
2 x 100k resistor
2 branch 100V line ELD
1 x 100V Speaker Line Warning Label (LB0648)
OPERATION
Operation of T-GEN is controlled by the Auto/Isol/Evac (AIE-
) input. In the “Auto” position the Alar
m input (ALM-) is
enabled. In the “Isol” (Isolate) position the Alarm input is disabled and any latched fault or alarm conditions are reset. In
the “Evac” position the Evacuate tone is generated.
In Auto mode activation of the Alarm input starts a six stage rising amplitude Alert tone. This continues until one of the
following occurs:
- the Alarm input returns to normal (Alarm input in non-latching mode), or
- the AIE- input is changed to Isol, or
- the AIE- input is changed to Evac, or
- the Alert to Evacuate change-over time is reached.
If the Alert to Evacuate change-over time is set to 0 sec, then no Alert tone is generated and the Evacuate tone is
generated immediately. If the change-over time is set to Alert only, no Evacuate tone is generated and must be initiated