Vigilant BOWS Installation & Operation Manual                                         Document: LT0554 

 

Page  

6 September 2012 

Issue 1.20 

iv 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

THIS PAGE INTENTIONALLY LEFT BLANK

Содержание LT0554

Страница 1: ...Building Occupant Warning Systems BOWS Installation Operation Manual LT0554 Issue 1 20 ...

Страница 2: ...Vigilant BOWS Installation Operation Manual Document LT0554 Page 6 September 2012 Issue 1 20 ii THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 3: ...on Operation Manual Issue 1 20 6 September 2012 Page iii Table of Contents Chapter 1 Introduction 1 1 Chapter 2 Operation 2 1 Chapter 3 Configuration 3 1 Chapter 4 Installation Wiring 4 1 Chapter 5 Diagnostics 5 1 Chapter 6 Specifications 6 1 ...

Страница 4: ...Vigilant BOWS Installation Operation Manual Document LT0554 Page 6 September 2012 Issue 1 20 iv THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 5: ... Diagram The BOWS has a microphone for emergency public address fault and status indicators and an Evacuation Control key switch to select its operating mode It has audio inputs for background music remote audio which can be used when streaming audio over IP networks and non emergency paging zone selective with an add on option The BOWS has a 24V 5A power supply battery charger compatible with 17A...

Страница 6: ...P1022 100W BOWS in the field The BOWS can optionally be fitted with a speaker distribution module SDM 4 which allows the single 100V 50W 100W output to be split into four separately selectable 100V line outputs Each output has separate line supervision o c s c The SDM 4 will isolate a shorted output allowing the other outputs to operate Each output is rated at 40W max The total load cannot exceed ...

Страница 7: ...ing the paging console to the BOWS This cable can be up to 300m in length Refer to the BOWS Zone Paging Kit Installation Guide LT0558 supplied with the kit for further details The BOWS supports zone selectable paging using the Emergency PA Microphone For this paging option the FP1024 EMERGENCY MIC ZONE PAGING KIT is required This kit includes all the required parts including SDM 4 Speaker Distribu...

Страница 8: ...Vigilant BOWS Installation Operation Manual Document LT0554 Page 6 September 2012 Issue 1 20 1 4 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 9: ...nd Indicators The BOWS has 5 indicators on the front panel as shown in Table 1 Table 1 BOWS Front Panel Indicators Indicator Colour Description Power On Green On when power is on Alarm Red Alarm input ALM is activated by the fire alarm system Isolated Blue Evacuation Control switch is in the ISOLATE position Audio Fault Yellow 100V speaker line is open or short circuit or amplifier fault Power Sup...

Страница 10: ...re automatically inserted in the Alert and Evacuate tone sequences respectively Messages shorter than 0 5 seconds are not inserted Generally with the Evacuation Control switch in the AUTO position the operation of the BOWS is controlled via the ALM input from the fire panel A test mode is provided for testing the 100V line and speakers To activate this put the BOWS into Auto and fit the Test Link ...

Страница 11: ...dicators Figure 8 Talk switch Off Microphone is turned off Page Microphone is turned on turns off when released Lock On Microphone is turned on Zone Select switches Push to select deselect a zone A blue indicator on the button is turned on when the zone is selected All Call Selects all 4 zones Cancel Deselects all zones Busy indicator Turned on if the console is not ready for paging Operation Sele...

Страница 12: ... emergency PA microphone To use this feature the FP1024 BOWS EMERGENCY MIC ZONE PAGING KIT option includes an SDM 4 must have been installed Operation Select the zone to be paged using the PAGING ZONE SELECT switch Figure 9 Make the announcement using the BOWS Emergency PA microphone by pushing the microphone s push to talk button Zone by zone paging is available only when the BOWS is not in Alarm...

Страница 13: ...e is being used The BOWS has a 3 5mm audio jack and screw terminals for connecting an external remote audio source to the BOWS The remote audio input has an Active input signal which must be activated by the external audio source to broadcast the audio The remote audio input can be configured to either override the T GEN tones similar to the emergency PA microphone or not override tones similar to...

Страница 14: ...Vigilant BOWS Installation Operation Manual Document LT0554 Page 6 September 2012 Issue 1 20 2 6 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 15: ...1 The operation of the BOWS is configured via links on the BOWS Interface board and an 8 way DIP switch and links on the Master T GEN 50 Figure 10 View inside 50W BOWS cabinet Chapter 3 Configuration Summary Power Supply T GEN 50 master BOWS Interface Board T GEN 50 slave mounted here when fitted ...

Страница 16: ...D or LOW When 2 or more audio sources are selected at the same time this priority determines which source will be played The valid combinations are shown in Table 2 Table 2 BOWS Interface Priority Links LK1 Paging LK2 Remote Audio LK3 Emergency Mic Comment LOW MED HI Factory default LOW HI MED MED HI LOW MED LOW HI HI MED LOW HI LOW MED HI LOW or MED HI Emergency PA Mic used for paging If any othe...

Страница 17: ...io Source Link Position ACTIVE Input Operation LK6 Remote Audio No 30V to 2V Inactive 2V to 30V Active Factory default Yes 30V to 1V Active 1V to 30V Inactive Note that on Issue A boards the ACTIVE input is always active High The BOWS Interface board has the following 3 volume adjustment controls as listed in Table 5 Table 5 BOWS Interface Volume Controls Control Name Function VR1 BM VOL Backgroun...

Страница 18: ...0 has 3 level adjustment controls as shown in Table 6 Table 6 T GEN 50 Level Controls Control Name Function VR1 BIAS Amplifier Bias Factory adjust only VR2 SPEECH VOL Volume adjustment for recorded messages VR3 PA VOL Volume adjustment for emergency PA microphone Note that the BIAS VR1 level must not be adjusted T GEN 50 Master Level Controls SW1 Configuration Switch LK4 Test Link Play Button LK3 ...

Страница 19: ...vacuate the building using the nearest fire exit Msg2 Evacuate as directed x2 Alert The fire alarm system has operated Standby for further instructions ISO8201 Keywords Emergency Evacuate Now The T GEN 50 has 7 links for configuring options such as Master Slave operation as shown in Table 8 Test Tone generation and recording messages Generally only the REC EN and TEST links should be changed on th...

Страница 20: ...is released or the maximum message length has been reached see NOTE 4 The recorded message can be played back using the Play button on the T GEN board Note that if the Evacuation Control switch is not in the Isolate position the played back message will be broadcast over the speaker system Recording is not broadcast 5 When recording has been completed re set T1 to its original position and remove ...

Страница 21: ...r until failure then every half hour until success Battery Low capacity is latching until successful retest 3 ON Switch ON to enable self timed Battery Disconnected and Battery Low Capacity tests 4 OFF Switch ON to enable earth fault detection Only for current production versions with firmware SF0445 version V1 1 or later Switching this off will leave any other earth fault detection unaffected 5 O...

Страница 22: ...Vigilant BOWS Installation Operation Manual Document LT0554 Page 6 September 2012 Issue 1 20 3 8 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 23: ...t is typically fixed to a wall with four 6 mm screws or bolts not included The drilling details are shown in Figure 13 The following conditions are required 1 Dry Area moderate ambient temperature 45 C maximum 2 Not exposed to direct sunlight 3 Not subject to outdoor conditions without suitable protection 4 The display should be at average eye level and must not be higher than 1850 mm or lower tha...

Страница 24: ...ling the circuit boards This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 430 102 o o o 6 0 o 6 0 280 o o o 6 0 o 6 0 1750 MAX 1220 MIN ALL DIMENSIONS IN MILLIMETRES FINISHED FLOOR LEVEL Figure 13 BOWS Cabinet Mounting Details ...

Страница 25: ...wired by a suitably qualified technician IMPORTANT The factory fitted earth loom under the mounting block must be wired to the earth terminal of the mains outlet in order to correctly earth the BOWS cabinet The cabinet has space for a pair of 12V 17Ah batteries which will provide over 24hrs standby and hr alarm load for a 100W system with paging This should be sufficient for most systems The BOWS ...

Страница 26: ... Description 1 0V Signal ground 2 ALM Alarm input signal Pulled to 0V to put the BOWS into Alarm The BOWS has a common fault relay Table 11 which is normally energised when the BOWS is powered up and normal not in fault This relay is de energised on Audio Fault e g 100V speaker line fault Power Supply Fault e g battery fault Loss of power mains battery The Evacuation Control switch in the ISOLATE ...

Страница 27: ...acitor Figure 15 Speaker Wiring 100V Line Output 100V a c audio line wiring is defined as LV Telecommunications circuits and is subject to the Australian Standard AS ACIF S009 2006 Ensure that this wiring is appropriately separated and insulated from LV power wiring ELV and other customer cabling such as detection and control circuits 100V wiring is required to be double insulated If the FP1021 50...

Страница 28: ...ic input is located on the BOWS Interface board as shown in Figure 17 A level adjustment control VR1 is provided to adjust the output volume Two connection options are available a 3 5mm audio socket J11 b screw terminals on connector J24 Table 12 The audio socket is a stereo socket The BOWS will combine the left and right channels to provide a single mono output Note that if a mono plug is inserte...

Страница 29: ...s a stereo socket The BOWS will combine the left and right channels to provide a single mono output Note that if a mono plug is inserted the effective audio level will be halved Table 13 BOWS Interface Remote Audio Screw Terminals 0V 0V RA SIG Remote Audio Signal The input will support audio levels up to 1Vrms and will allow maximum output volume at an input level of approximately 200mVrms Remote ...

Страница 30: ... a paging console input that is used with the paging options to provide zone selective paging The connector J16 PAGING CONSOLE is an RJ45 socket with terminals as shown in Table 14 Table 14 BOWS Interface Paging Console Inputs Pin Function Description 1 V Power to Paging Console 24V 2 0V 3 Line Cold Balanced Audio from Paging Console 1Vrms max Input impedance 600Ω 4 Line Hot 5 Zone Sel 1 Zone sele...

Страница 31: ...Output IOR F3200 etc Input IOR ADR ADM13X etc EOLR 10K ALM 0V Relay Output F3200 Relay Bd IOR ADC130 EOLR 10K FLT FLT 0V 0V FP1600 MK3 Sigma5 Omega64 MK3 See Note3 E g PA0729 GP Relay Board ALM 0V 12V RELAY FLT 10K FLT0V ALM BELLS C BELLS Notes 1 EOLR value depends upon the fire alarm system s input type Not fitted when used with MX1 or 4100ES 2 Switch SW4 ON on the master T GEN 3 FP1600 Omega 64 ...

Страница 32: ...t Wiring Notes 1 3k3 EOLR for MX4428 Ancil Relay and RRM F3200 Ancil Relay and RRM 2k5 3k3 10k for F3200 Bells 2 AAR must be inside FIP and wired to RESP IN 3 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 4 Turn T GEN master SW4 off 5 Cut Ancil Sup link on F4000 MX4428 Main Board BOWS Note 4 ALM NO COM 0V EOLR Note 1 0V Fault Relay ALM F4000 MX4428 ...

Страница 33: ...ure 23 SIMPLEX 4090 9118 Relay IAM Wiring The relay must be configured as a Signal Output and the T SENSE input as a Fault Point The Relay IAM can be mounted inside the BOWS cabinet Please refer to the Programming Guide for your panel type for further details SIMPLEX 4100 4100U 4100ES Fire Alarm Panel Wiring 4100 3003 4100 3204 Relay Module 4090 9118 Relay IAM Note 1 Switch SW4 ON on the master T ...

Страница 34: ...ded on the gear plate This T GEN must be configured as a slave and wired to the PSU and master T GEN as per Figure 24 Figure 24 Wiring the T GEN Slave The SIG and DEF inputs on the slave must be connected to the SIG and DEF inputs on the master T GEN respectively The 2nd 100V speaker line is connected to the slave T GEN 100V Line Line terminals NAC Installing a Second T GEN 50 in the FP1021 50W BO...

Страница 35: ...ments to 1 or more slave BOWS connected together on a LAN For this application an Annuncicom 200 is used in the master BOWS and either an Annuncicom 200 or Exstreamer 100 at each slave BOWS as shown in Figure 25 Figure 25 Master BOWS connected to multiple slave BOWS At the master BOWS the Annuncicom 200 is connected to the BOWS Interface board as per Figure 26 The J15 TO T GEN MICROPHONE signals f...

Страница 36: ...d Pin 2 24Vdc LAN Figure 26 Annuncicom Wiring at the master BOWS An Annuncicom 200 or an Exstreamer 100 is used at each slave BOWS As the Exstreamer is generally less expensive it would normally be used at the slave BOWS Figure 27 shows how to wire an Exstreamer 100 to the BOWS Interface board at a slave Figure 27 Wiring an Exstreamer 100 to the Slave BOWS Remote Audio Input REMOTE AUDIO BOWS Inte...

Страница 37: ...control the ACTIVE signal on the Remote Audio port If the PA announcements are not required to override the Alert Evacuation tones at the slave BOWS the audio output of the module can be connected to the background music input on the Slave BOWS as shown in Figure 29 Figure 29 Wiring an Exstreamer 100 to the Slave BOWS Background Music Input Please refer to BOWS IP Networking Manual LT0561 for furt...

Страница 38: ...Vigilant BOWS Installation Operation Manual Document LT0554 Page 6 September 2012 Issue 1 20 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 39: ...er and slave T GEN faulty T GEN Amplifier faulty or over loaded If a slave T GEN FAULT LED is on check the following 100V line open or short circuit EOL resistor missing from the end of the 100V line Note that on the 100W BOWS a 56k EOL resistor is fitted directly across the 100V line terminals of the slave T GEN SIG wire between the master and slave T GEN faulty T GEN Amplifier faulty or over loa...

Страница 40: ...h Fault A temperature sensor open or short circuit is indicated by Charger High and Charger Low indications at the same time Note that the audio sources are disabled when the Evacuation Control switch is in the ISOLATE position The background music remote audio and paging inputs on the BOWS Interface board have individual volume controls Check that the volume control is set correctly turn clockwis...

Страница 41: ...t 3V 5V if supervision enabled 3k3 10k Normal 1V 3V S C Alarm 0V 1V Input Current 0 7mA at 0V Fault Output FLT Normal FLT O C Fault FLT 0V ELV only 30V 2Adc max COM NO NC Normal COM NO Fault COM NC Voltage free contacts ELV only 30V 2Adc resistive max 30V 1Adc inductive max Audio Inputs Background Music Non isolated Input impedance 10k 0 2Vrms min 1Vrms max for full power Remote Audio Remote Audio...

Страница 42: ...ply with AS1670 1 clause 3 22 b Part Numbers FP1021 BOWS 50W FP1022 BOWS 100W FP1023 BOWS Zone Paging Kit C W SDM 4 and Paging Console FP1024 BOWS Emergency Mic Zone Paging Kit C W SDM 4 and Zone Selector Switch PA0766 T GEN 50 for FP1021 or as spare part PA1090 BOWS Interface Board spare part ME0476 PSU spare part keep loom in BOWS that plugs into J7 of PSU ...