Document: LT0554
Vigilant BOWS Installation & Operation Manual
Issue 1.20
6 September 2012
Page 4-11
The BOWS can be wired to a SIMPLEX 4100-3003 / 4100-3204 Relay
Module as shown in Figure 22.
Figure 22. SIMPLEX 4100-3003 Relay Module Wiring
The relay must be configured as a Signal Output, and the FB input as a
Fault Point. Please refer to the
Programming Guide
for your panel type for
further details.
The BOWS can be wired to a SIMPLEX 4090-9118 Relay IAM as shown
in Figure 23.
Figure 23. SIMPLEX 4090-9118 Relay IAM Wiring
The relay must be configured as a Signal Output, and the T-SENSE input
as a Fault Point. The Relay IAM can be mounted inside the BOWS
cabinet. Please refer to the Programming Guide for your panel type for
further details.
SIMPLEX 4100+/4100U/4100ES Fire Alarm Panel Wiring
4100-3003/
4100-3204
Relay
Module
4090-9118
Relay IAM
Note 1. Switch SW4 ON on the master T-GEN.
Note 1. Switch SW4 ON on the master T-GEN.
4100
4100-3003/
4100-3204
Relay
Module
NO
0V
ALM-
(see note 1)
BOWS
NC
10k EOL
COM
Fault
Relay
NO
COM
FB
SPS Aux Power 0V
4090-9118
Relay IAM
Relay
1
IDNet
NC
10k EOL
COM
0V
ALM-
(see note 1)
BOWS
Fault
Relay
COM
NO
NC
6k8 EOL
T-SENSE
NO
2