Heating characteristics
Measures
Example
The living space is
too cold
during the heating sea-
son
.
Adjust the heating curve
slope
to the
next high-
est
value (e.g. 1.5).
Slope
1.5
Level
0 K
The living space is
too hot
during the heating sea-
son
.
Adjust the heating curve
slope
to the
next lowest
value (e.g. 1.3).
Slope
1.3
Level
0 K
The living space is
too cold
during spring/autumn
and
during the
heating season
.
Adjust the heating curve
level
to the
next high-
est
value (e.g. +3).
Slope
1.4
Level
3 K
The living space is
too hot
during spring/autumn
and
during the
heating season
.
Adjust the heating curve
level
to the
next lowest
value (e.g. −3).
Slope
1.4
Level
-3 K
The living space is
too cold
during spring/autumn
, but
warm enough during the
heating season.
Adjust the heating curve
slope
to the
next lowest
value and the
level
to a
higher
value.
Slope
1.3
Level
3 K
The living space is
too hot
during
spring and autumn
,
but warm enough during the
heating season.
Adjust the heating curve
slope
to the
next high-
est
value and the
level
to
a
lower
value.
Slope
1.5
Level
-3 K
Press the following keys:
1.
å
for the "Extended menu".
2.
|
/
~
to select
"Heating"
.
3.
d
to confirm.
4.
Ù
/
Ú
to select
"Heating cir-
cuit 1"
(HC1),
"Heating cir-
cuit 2"
(HC2),
"Heating cir-
cuit 3"
(HC3) or
"Heating
circuit 4"
(HC4, if instal-
led).
5.
|
/
~
for
"Heating curve"
.
6.
d
to confirm.
7.
|
/
~
for
"Slope"
or
"Level"
.
8.
d
to confirm.
Central heating
Changing the heating curve
(cont.)