53
Coding in the delivered condition
Possible change
E7:30
Minimum speed of the
variable speed pump
30 % of max. speed
E7:0
to
E7:100
Minimum speed adjustable
from 0 to 100 % of max.
speed
E8:1
Minimum speed subject
to the setting in coding
address "E9"
E8:0
Speed subject to the set-
ting in coding address
"E7"
E9:45
Speed of the variable
speed pump 45 % of max.
speed in reduced mode
E9:0
to
E9:100
Speed adjustable from 0 to
100% of max. speed
F1:0
Screed function disabled F1:1
to
F1:6
Screed drying function
adjustable in accordance
with 6 optional tempera-
ture/time profiles (see
page 84)
F1:15
Constant flow temperature
20 °C
Mixer circuit
F2:8
Time limit for party mode
8 hours or external oper-
ating mode changeover
via key
*2
F2:0
No time limit for party mode
F2:1
to
F2:12
Time limit adjustable from 1
to 12 h
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode
F5:0
No run-on time for the inter-
nal circulation pump
F5:1
to
F5:20
Run-on time of the internal
circulation pump adjusta-
ble from 1 to 20 min
*2
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
Codes
Code 2
(cont.)
5692 799 GB